Skip to main content
Schneider Electric MGN60521

MGN60521 C60N MCB, D Curve 6 A 2P, 20 kA Breaking

MPN MGN60521
Obsolete

Schneider Electric C60N Multi9 miniature circuit breaker, MGN60521, D curve, 6 A rated, 2 poles, 20 kA Icu at 240 V AC, thermal-magnetic trip, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60521 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN60521 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

What the D curve and 6 A rating mean for your panel

The MGN60521 is a C60N miniature circuit breaker from the Multi9 range, rated 6 A at 50 °C with a D tripping curve. The 6 A thermal element protects the downstream cable against sustained overloads; the magnetic element clears short-circuits fast enough to keep the fault energy within the cable's withstand rating. Breaking capacity is 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V — all conforming to EN/IEC 60947-2. For a 240 V distribution board fed from a transformer with a prospective short-circuit current under 20 kA, this breaker provides full discrimination upstream.

Occupies 4 modules of 9 mm pitch (36 mm total width). The 73 mm depth and 81 mm height fit standard distribution enclosures. Pollution degree 3 per EN/IEC 60947-2 means it's rated for the conductive-dust environment inside a typical industrial panel.

IP20 finger-safe protection on the front face. Storage temperature range -40 to 80 °C, operating ambient -30 to 70 °C. The D curve and 2-pole configuration make it a direct fit for 240 V split-phase or 415 V phase-to-phase motor branch circuits where a C curve would trip on inrush.

MPN