Schneider Electric MGN60614 — 1-Pole MCB (DIN Rail)

Schneider Electric MGN60614 C60H MCB, 16 A, 1P, C-Curve, 15

MPNMGN60614
Obsolete

Schneider Electric Multi9 C60H series, MGN60614 miniature circuit breaker, 1-pole, 16 A, C-curve, 15 kA breaking capacity at 240 V AC, thermal-magnetic trip, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60614 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60614 — Electrical & Protection
ParameterValue
Rated current (In)16 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral 415 V AC 50/60 Hz phase to phase
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 24 kA Icu at 60 V DC phase to phase conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60614 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN60614 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60614 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The Schneider Electric MGN60614 is a C60H miniature circuit breaker from the Multi9 range, rated 16 A at 50 °C per EN/IEC 60947-2. The C-curve means magnetic tripping occurs between 5 and 10 times rated current (8.5 x In +/- 20 % here), making it the standard choice for motor-starter and distribution circuits where inrush is moderate. The 1-pole format protects a single phase or DC leg.

Width is 18 mm (2 x 9 mm pitches), so it occupies one module position. IP20 finger-safe front, pollution degree 3 per EN/IEC 60947-2, so it's rated for the typical industrial control panel environment. Toggle switch with ON/OFF indication and a contact-position indicator for visual confirmation of isolation state.

Frequently asked questions

How do I get current pricing and availability for MGN60614?

Submit an RFQ against this order code. We confirm current pricing and availability at quote time through our franchise distribution channel.

What is MGN60614's breaking capacity?

The MGN60614 is rated 15 kA Icu at 240 V AC phase-to-neutral and 24 kA Icu at 60 V DC phase-to-phase, both per EN/IEC 60947-2. The service breaking capacity Ics is 7.5 kA (50 %) at 240 V AC and 24 kA (100 %) at 60 V DC.

What compliance documentation does this brand provide for MGN60614?

The MGN60614 is designed and tested to EN/IEC 60947-2. It carries a pollution degree 3 rating and IP20 protection. Standard Schneider Electric documentation includes the declaration of conformity and test certificates available through the franchise channel.

MPN
MGN60614