MGN60618 Schneider C60H MCB, 1P C-Curve 40 A, 15 kA

MPNMGN60618
Obsolete

Schneider Electric Multi9 C60H series, MGN60618 miniature circuit breaker, 1P, C-curve, 40 A, 15 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60618 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60618 — Electrical & Protection
ParameterValue
Rated current (In)40 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral 415 V AC 50/60 Hz phase to phase
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 24 kA Icu at 60 V DC phase to phase conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60618 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 3.5 N.m
MGN60618 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60618 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN60618 is a Schneider Electric C60H miniature circuit breaker in the Multi9 range, rated 40 A at 50 °C with a C trip curve (magnetic tripping limit 8.5 x In ±20 %). The 15 kA Icu at 240 V AC phase-to-neutral (EN/IEC 60947-2) means this breaker can safely interrupt a fault current up to that level without welding its contacts or rupturing the arc chamber; the 7.5 kA Ics (service breaking capacity) at the same voltage tells you it can reclose and carry rated current after one fault operation. At 60 V DC the Icu rises to 24 kA, so it handles DC distribution in telecom or battery-backed circuits. The IP20 finger-safe enclosure suits enclosed panel installation — not washdown or outdoor exposure. Ambient operating range -30 to 70 °C covers most control-room and switchboard environments; storage range -40 to 80 °C.

Certified to EN/IEC 60947-2 (pollution degree 3, utilisation category A). Suitability for isolation is declared per the same standard. Earth-leakage protection requires a separate block. Tunnel-type terminals accept 1.5 to 35 mm² flexible or rigid conductors; tightening torque is 3.5 N·m. The manufacturer's declaration of conformity and full test reports are available on request with the RFQ.

Frequently asked questions

How do I get current pricing and availability for MGN60618?

The MGN60618 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What is the breaking capacity of MGN60618?

The MGN60618 has a 15 kA Icu at 240 V AC phase-to-neutral and 24 kA Icu at 60 V DC, both conforming to EN/IEC 60947-2. The service breaking capacity Ics is 7.5 kA (50 %) at 240 V AC and 24 kA (100 %) at 60 V DC.

What compliance documentation does MGN60618 carry?

The MGN60618 is certified to EN/IEC 60947-2 (pollution degree 3, utilisation category A) and is declared suitable for isolation per that standard. The manufacturer's declaration of conformity and test reports are available on request with the RFQ.