Skip to main content
Schneider Electric MGN60621 — 2-Pole MCB (DIN Rail)

Schneider Electric MGN60621 C60H MCB, 1 A C-Curve, 2P, 30 kA

MPNMGN60621
Obsolete

Schneider Electric Multi9 C60H series, MGN60621, miniature circuit breaker, 1 A rated, C-curve, 2-pole, 30 kA Icu at 240 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60621 — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN60621 — Electrical
ParameterValue
Rated current [In]1 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
MGN60621 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu)30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN60621 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Comb busbar / distribution block compatibilityTop or bottom: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN60621 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
MGN60621 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

What this MCB brings to the panel

The Schneider Electric MGN60621 is a C60H miniature circuit breaker from the Multi9 range, rated 1 A at 50 °C per EN/IEC 60947-2 with a C-curve (magnetic trip at 8.5 x In ±20 %). Its 2-pole configuration and 30 kA Icu at 240 V AC phase-to-phase mean it can clear high fault currents on a 240 V distribution bus without upstream coordination headaches — the 50 % Ics rating (15 kA at 240 V AC) tells you it's rated for repeated fault clearing, not just one-shot isolation. The 35 mm DIN-rail mount and 36 mm width (4 x 9 mm pitches) fit standard panel layouts; tunnel terminals accept 1–25 mm² conductors, so it handles both control-circuit tails and feeder-size cable.

Snaps onto 35 mm symmetrical DIN rail (EN 60715). The fixed mounting mode and IP20 finger-safe terminals make it a standard panel component. Comb busbar compatible top or bottom, so daisy-chaining multiple poles or adjacent breakers is straightforward.

Frequently asked questions

Where can I buy MGN60621?

We source MGN60621 to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of MGN60621?

30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V AC, 10 kA at 440 V AC, and 25 kA at 125 V DC — all per EN/IEC 60947-2. The Ics (service breaking capacity) is 50 % of Icu at AC voltages and 100 % at 125 V DC.

What compliance documentation does Schneider provide for MGN60621?

The breaker is certified to EN/IEC 60947-2 with pollution degree 3. It carries an IP20 rating and is suitable for isolation per the same standard. Specific RoHS/REACH/UL documentation should be requested at quote time.

MPN
MGN60621