Schneider Electric MGN60627 — 2-Pole MCB (DIN Rail)

MGN60627 C60H MCB, 2P 16A C-Curve, 30 kA

MPNMGN60627
Obsolete

Schneider Electric Multi9 C60H series, MGN60627, 2-pole miniature circuit breaker, 16 A rated current, C-curve, 30 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60627 — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN60627 — Electrical
ParameterValue
Rated current [In]16 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
MGN60627 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu)30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN60627 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Comb busbar / distribution block compatibilityTop or bottom: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN60627 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
MGN60627 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

C60H 2P 16A MCB — distribution panel fit

The MGN60627 is a 2-pole C60H miniature circuit breaker from the Multi9 range, rated 16 A at 50 °C with a C-curve trip characteristic (magnetic trip at 8.5 x In ±20 %). The 15 kA Icu at 415 V AC and 10 kA at 440 V AC cover the common European 400 V three-phase distribution voltages. For DC circuits, it holds 25 kA Icu at 125 V DC, so it handles battery-bank or solar-string protection in the same footprint. The utilisation category is Category A per EN/IEC 60947-2, meaning it is not intended for selective coordination under short-circuit conditions; the downstream breaker trips faster than the upstream one by design, which is the normal arrangement for final subcircuits. Mounts on a 35 mm symmetrical DIN rail, occupies 4 x 9 mm pitches (36 mm width), and accepts tunnel-type terminals up to 25 mm² rigid or flexible. The contact position indicator and ON/OFF local signalling give a visual confirmation of state without needing to measure voltage, which speeds fault isolation during commissioning or troubleshooting.

If the panel ambient runs higher than 50 °C, derate per the manufacturer's thermal curve (not supplied here, but the operating range of -30 to 70 °C gives the thermal envelope). The 10,000-cycle electrical endurance and 20,000-cycle mechanical endurance are typical for distribution-grade MCBs; this is not a switching device for frequent load cycling — use a contactor for that duty. The Ics (service breaking capacity) is 50 % of Icu at AC voltages — 15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V — but 100 % (25 kA) at 125 V DC. After clearing a fault at Ics level, the breaker is expected to remain operational, not just safe. For DC circuits, the 100 % Ics means it can handle repeated faults on battery or solar strings without replacement after each event. The contact position indicator and ON/OFF signalling provide visual confirmation of the isolation state — important for lockout/tagout procedures during maintenance.

Frequently asked questions

How do I get current pricing and availability for MGN60627?

The part is sourced and quoted to order against an RFQ. Submit a request for quote (RFQ) through the storefront; current pricing and availability are confirmed at quote time. No stock count or lead-time figure is published here, but the part is not subject to allocation or phase-out.

What compliance documentation does MGN60627 carry?

The MGN60627 is certified to EN/IEC 60947-2. It carries IP20 finger-safe protection and is suitable for isolation per that standard. For specific RoHS, REACH, or UL documentation, the manufacturer's compliance declarations are available on request — no conflict with the standard's requirements is expected for a current-production Multi9 part.

What is MGN60627's breaking capacity at different voltages?

The MGN60627 has a 30 kA Icu at 240 V AC, 15 kA at 415 V AC, 10 kA at 440 V AC, and 25 kA at 125 V DC, all per EN/IEC 60947-2. The Ics (service breaking capacity) is 50 % of Icu at AC voltages and 100 % at 125 V DC.

What is the C-curve trip characteristic on this MCB?

The C-curve has a magnetic tripping limit of 8.5 x In ±20 %, meaning it trips instantaneously between roughly 11 A and 19 A for the 16 A rating. This suits moderate inrush loads like small motors, transformers, and lighting circuits.