Skip to main content
Schneider Electric MGN60630

Schneider Electric MGN60630 C60H MCB, 32 A, 2P, C-Curve, 30

MPN MGN60630
Obsolete

Schneider Electric Multi9 C60H, MGN60630, 2-pole miniature circuit breaker, 32 A rated current, C-curve, 30 kA breaking capacity at 240 V AC, thermal-magnetic trip, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60630 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN60630 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The Schneider Electric MGN60630 is a C60H miniature circuit breaker from the Multi9 range, rated 32 A at 50 °C with a C-curve trip characteristic. Thermal-magnetic trip unit, Category A utilisation per EN/IEC 60947-2. The C-curve means magnetic tripping between 5 and 10 times In (here 8.5 x In ±20 %), so it handles moderate inrush from motor starters or lighting ballasts without nuisance trips.

Breaking capacity and service continuity

Rated ultimate breaking capacity (Icu) hits 30 kA at 240 V AC phase-to-phase, 15 kA at 415 V AC, and 10 kA at 440 V AC. On the DC side, 25 kA at 125 V DC. Service breaking capacity (Ics) is 50 % of Icu for AC voltages — 15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V — and 100 % at 125 V DC (25 kA). That means after clearing a fault at the Ics level, the breaker remains functional and can be reclosed without immediate replacement.

Snaps onto 35 mm symmetrical DIN rail. Tunnel terminals accept 1.5 to 35 mm² flexible with or without cable end, or rigid. IP20 finger-safe protection.

MPN
MGN60630