Schneider Electric MGN60868 — 1-Pole MCB (DIN Rail)

MGN60868 C60N MCB, C Curve 16 A 1P, 10 kA Breaking Capacity

MPNMGN60868
Obsolete

Schneider Electric Multi9 C60N miniature circuit breaker, MGN60868, 1P, 16 A, C curve, 10 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60868 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60868 — Electrical & Protection
ParameterValue
Rated current (In)16 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60868 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN60868 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60868 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN60868 is a C60N miniature circuit breaker from the Multi9 range, rated 16 A with a C curve trip characteristic and a single protected pole. The 10 kA Icu at 240 V AC phase-to-neutral (per EN/IEC 60947-2) means it can safely interrupt a fault up to that level without welding its contacts — enough headroom for most service-entrance and sub-panel applications. The C curve magnetic trip at 8.5 x In (±20%) handles motor inrush and moderate inductive loads without nuisance tripping.

The 18 mm width (2 x 9 mm pitches) fits standard DIN-rail enclosures. Tunnel terminals accept 1 to 25 mm² rigid or flexible wire; strip length is 14 mm, tighten to 2 N·m. The toggle handle gives clear ON/OFF indication and a contact position indicator confirms the state of the main contacts. IP20 finger-safe terminals are fine for enclosed panels — no washdown rating here.

Frequently asked questions

What is the breaking capacity of MGN60868?

The MGN60868 has a breaking capacity of 10 kA Icu at 240 V AC and 3 kA Icu at 415 V AC, both phase-to-neutral per EN/IEC 60947-2.

Where can I buy MGN60868?

MGN60868 is sourced through independent distribution channels and quoted to order against an RFQ — availability and current pricing are confirmed at quote time.

What is the rated current and curve of MGN60868?

The rated current is 16 A at 50 °C per EN/IEC 60947-2, with a C curve magnetic trip at 8.5 x In (±20%).