Skip to main content
Schneider Electric MGN60870 — 1-Pole MCB (DIN Rail)

MGN60870 C60N Miniature Circuit Breaker, 25 A, 1P, C-Curve

MPNMGN60870
Obsolete

Schneider Electric Multi9 C60N, MGN60870, miniature circuit breaker, 1P, 25 A, C-curve, 10 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60870 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60870 — Electrical & Protection
ParameterValue
Rated current (In)25 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60870 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN60870 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60870 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN60870 is a Schneider Electric C60N miniature circuit breaker from the Multi9 range, rated 25 A at 50 °C per EN/IEC 60947-2. The C-curve means magnetic tripping occurs between 5 and 10 times rated current (8.5 x In ±20 % per the spec), so it's sized for general-purpose distribution loads like lighting, socket circuits, and small motor feeders where inrush isn't extreme. The 1-pole (1P) configuration protects one phase; the neutral is switched separately if needed. Breaking capacity is 10 kA Icu at 240 V AC phase-to-neutral, with a service breaking capacity (Ics) of 7.5 kA (75 %) at the same voltage — meaning after clearing a fault at that level the breaker remains functional, not just safe. The part is rated Category A per EN/IEC 60947-2, which covers general distribution without specific short-time delay requirements.

Width is 18 mm (2 x 9 mm pitches), so it occupies one module position. Depth is 73 mm, height 81 mm. IP20 rated, so it's for dry indoor enclosures only. Pollution degree 3 per EN/IEC 60947-2 means it's suitable for environments with conductive or dry non-conductive pollution — typical for most industrial control panels.

Frequently asked questions

How do I get current pricing and availability for MGN60870?

Submit an RFQ against this part number. We source through the authorized Schneider Electric channel and confirm current pricing and availability at quote time for your specific quantity and delivery window.

What is MGN60870's breaking capacity at 240 V AC?

The MGN60870 has a breaking capacity (Icu) of 10 kA at 240 V AC phase-to-neutral per EN/IEC 60947-2, with a service breaking capacity (Ics) of 7.5 kA at the same voltage.

What compliance standards does MGN60870 meet?

The MGN60870 is designed and tested to EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear circuit breakers. It carries a pollution degree 3 rating and is suitable for isolation per that standard.

MPN
MGN60870