Skip to main content
Schneider Electric MGN60874 — 1-Pole MCB (DIN Rail)

MGN60874 C60N MCB, 1P, 63A, C-Curve, 10kA

MPNMGN60874
Obsolete

Schneider Electric Multi9 C60N series, MGN60874 miniature circuit breaker, 1P, 63 A, C-curve, 10 kA Icu at 240 V AC, 18 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60874 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60874 — Electrical & Protection
ParameterValue
Rated current (In)63 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60874 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 3.5 N.m
MGN60874 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60874 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

Schneider Electric MGN60874 is a C60N miniature circuit breaker from the Multi9 range — a 1-pole, 63 A thermal-magnetic MCB with a C-curve trip characteristic (magnetic trip at 8.5 x In ±20 %). It breaks 10 kA Icu at 240 V AC phase-to-neutral per EN/IEC 60947-2, with an Ics of 7.5 kA (75 %) at the same voltage. The 63 A rating at 50 °C gives you headroom for continuous loads without derating in a warm enclosure.

Occupies one module position in a standard distribution board — no extra gap needed for heat dissipation at 63 A. Tunnel terminals accept 1.5 to 35 mm² rigid or flexible (with/without ferrule); tighten to 3.5 N·m. Strip 14 mm of insulation. The IP20 finger-safe front is standard for enclosed panels.

Frequently asked questions

What is the breaking capacity of MGN60874?

10 kA Icu at 240 V AC phase-to-neutral per EN/IEC 60947-2, with a service breaking capacity (Ics) of 7.5 kA (75 %) at the same voltage. At 415 V AC the Icu drops to 3 kA.

Where can I buy MGN60874 and get current pricing?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for this order code.

What standards does MGN60874 comply with?

Designed and tested to EN/IEC 60947-2, pollution degree 3. Suitable for isolation per that standard, with a contact position indicator and ON/OFF local signalling.

MPN
MGN60874