The MGN60882: Rated Icu of 20 kA at 240 V AC phase-to-phase, 10 kA at 415 V AC, and 6 kA at 440 V AC — these are the maximum fault currents the breaker can safely interrupt.
Trip curve and application fit
C-curve magnetic trip at 8.5 x In (±20 %). Thermal element handles 20 A continuous at 50 °C.
IP20 finger-safe front; comb busbar compatible top or bottom. The 73 mm depth fits standard distribution board enclosures with gland-plate clearance.