Skip to main content
Schneider Electric MGN60883 — 2-Pole MCB (DIN Rail)

MGN60883 C60N MCB, 25 A, C Curve, 2P, 20 kA

MPNMGN60883
Obsolete

Schneider Electric Multi9 C60N, miniature circuit-breaker, 25 A, C curve, 2 poles, 20 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60883 — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN60883 — Electrical
ParameterValue
Rated current [In]25 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
MGN60883 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu)20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN60883 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Comb busbar / distribution block compatibilityTop or bottom: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN60883 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
MGN60883 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

What this MCB delivers on the panel

The MGN60883 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range, rated 25 A at 50 °C with a C curve (magnetic tripping at 8.5 x In ±20 %). Two poles protected, thermal-magnetic trip, tunnel terminals accepting up to 25 mm².

At 415 V AC the Icu drops to 10 kA, at 440 V to 6 kA. For a 240 V distribution panel with an upstream transformer sized for 10 kA available fault current, this C60N gives 10 kA of headroom before you need a current-limiting fuse upstream. The C curve (8.5 x In magnetic trip) suits mixed loads with moderate inrush — lighting banks, contactor coils, small motor circuits.

Fixed mounting on 35 mm symmetrical DIN rail. 4 module pitches (36 mm wide, 81 mm tall, 73 mm deep). Tightening torque 2 N·m on the power circuit. Wire strip length 14 mm. IP20 finger-safe terminals. Top or bottom comb busbar compatible. ON/OFF indication visible on the toggle.

Frequently asked questions

How do I get pricing and availability for MGN60883?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; current pricing and stock levels are confirmed at quote time.

What is the breaking capacity of MGN60883 at 240 V?

20 kA Icu at 240 V AC phase-to-phase per EN/IEC 60947-2, with an Ics of 15 kA (75 %).

What standards does MGN60883 comply with?

EN/IEC 60947-2, pollution degree 3. Suitable for isolation. IP20 rated.

What is the closest alternative to MGN60883 in the same family?

Within the C60 range, the closest sibling by rating and poles is the C60N 25 A 2P C curve — the MGN60883 is that exact variant. No pin-compatible alternative exists because the C60N is the standard production version; a different curve (B or D) or higher breaking capacity (C60H or C60L) changes the trip characteristic or SCCR, not the footprint.

MPN
MGN60883