Skip to main content
Schneider Electric MGN60884

MGN60884 C60N MCB, 32 A, Curve C, 2P, 20 kA

MPN MGN60884
Obsolete

Schneider Electric C60N miniature circuit breaker, Multi9 range, 32 A, C curve, 2 poles, 20 kA breaking capacity at 240 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60884 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN60884 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60884 is a C60N miniature circuit breaker from the Multi9 range, a workhorse series for distribution panels. It's a 2-pole thermal-magnetic MCB rated 32 A at 50 °C with a C curve (magnetic trip at 8.5 x In ±20 %). That C curve means it's built for moderate inrush — motor starters, small transformers, lighting banks — where the start-up spike sits above resistive loads but below the D-curve's heavy kick.

Breaking capacity and real-world fault handling

Breaking capacity: 20 kA at 240 V AC, 10 kA at 415 V AC, 6 kA at 440 V AC. Ics is 75 % of those figures — 15 kA, 7.5 kA, 4.5 kA respectively.

Mounts fixed on 35 mm DIN rail. Tunnel terminals accept 1.5 to 35 mm² — flexible with or without cable end, or solid. Strip length 14 mm, torque to 3.5 N·m. IP20 finger-safe front. The toggle gives local ON/OFF indication, and there's a contact position indicator for isolation duty — it's certified for isolation per the standard. Earth-leakage protection requires a separate block (not built in).

MPN
MGN60884