Skip to main content
Schneider Electric MGN60885

MGN60885 C60N MCB, 2P C-Curve 40 A, 20 kA Breaking

MPN MGN60885
Obsolete

Schneider Electric, Multi9 C60 series, C60N miniature circuit-breaker, MGN60885, 2-pole C-curve 40 A, 20 kA breaking capacity at 240 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60885 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

MGN60885 additional specifications
ParameterValue
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60885 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range, a 2-pole (2P) thermal-magnetic device rated 40 A at 50 °C per EN/IEC 60947-2. The C-curve trips magnetically at 8.5 x In (±20 %), so it holds through motor inrush and transformer energisation but clears a hard short inside half a cycle — the right characteristic for distribution circuits feeding mixed inductive and resistive loads, provided the downstream coordination study respects the 20 kA Icu at 240 V AC phase-to-phase. It is also rated for isolation, meaning the open contacts give a verifiable air gap that holds the unit on the grid during a lockout-tagout.

Breaking capacity follows the voltage: 20 kA Icu at 240 V AC, 10 kA at 415 V AC, 6 kA at 440 V AC — all phase-to-phase per EN/IEC 60947-2. For a 400/415 V distribution panel that means the MGN60885 coordinates downstream of a 25 kA-rated main breaker, provided the let-through energy of the upstream device stays below the 10 kA withstand of this pole. The 4-module width (36 mm, 4 x 9 mm pitches) fits standard DIN-rail enclosures without crowding the busbar feed.

Snaps onto 35 mm symmetrical DIN rail, fixed mounting only — no plug-in base. Tunnel-type terminals accept 1.5 to 35 mm² rigid or flexible (with or without ferrule); strip length is 14 mm, torque to 3.5 N·m. The IP20 finger-safe front is standard for enclosed panels; pollution degree 3 per EN/IEC 60947-2 means it tolerates conductive dust in industrial environments, provided the enclosure maintains the rated clearance. Comb busbars feed top or bottom. A separate earth-leakage block (Vigi) can be added on the load side for residual-current protection.

Environmental range and durability

Operates from -30 to 70 °C, stores from -40 to 80 °C — wide enough for unheated electrical rooms and outdoor enclosures in temperate climates. Mechanical endurance is 20,000 cycles; electrical endurance is 10,000 cycles at rated current per EN/IEC 60947-2, which for a distribution MCB in a panel that cycles infrequently translates to decades of service life. The toggle gives a local ON/OFF indication and the contact position indicator confirms the state without removing the cover.

MPN
MGN60885