Skip to main content
Schneider Electric MGN61311

MGN61311 Multi9 C60 Miniature Circuit Breaker, 0.5 A, C-Curv

MPN MGN61311
Obsolete

Schneider Electric Multi9 C60 miniature circuit breaker, MGN61311, 2-pole, 0.5 A rated current, C-curve, 10 kA breaking capacity per UL 489, gray, DIN-rail clip-on.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61311 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage480Y/277 V AC
Insulation voltage ui500 V AC EN/IEC 60947-2
Breaking capacity10 kA AIR 480Y/277 V AC UL 489 10 kA AIR 480Y/277 V AC CSA C22.2 No 5.2 10 kA Icu 480Y/277 V AC EN/IEC 60947-2 10 kA Icu 480Y/277 V AC GB 14048.2
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...176 °F (-40...80 °C)
Pollution degree3 EN/IEC 60947-2

All specifications

MGN61311 additional specifications
ParameterValue
ColorGray
Depth2.7 in (68.7 mm)
Width1.4 in (36 mm)
Height5.6 in (141 mm)
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-22...158 °F (-30...70 °C)

Product details

MGN61311 — Multi9 C60 0.5 A MCB, C-Curve, 2-Pole

The MGN61311 is a 2-pole miniature circuit breaker from the Schneider Electric Multi9 C60 range, rated 0.5 A at 77 °F (25 °C) with a C-curve trip characteristic (8.5 x In magnetic tripping limit, ±20 % on AC). It carries a 10 kA breaking capacity under UL 489 at 480Y/277 V AC, and is also rated 10 kA Icu per EN/IEC 60947-2 and GB 14048.2.

Clip-on mounting onto DIN rail (35 mm per EN 60715) — occupies 4 x 9 mm pitches (36 mm width). The 2.7 in (68.7 mm) depth and 5.6 in (141 mm) height fit standard distribution board cutouts. Tunnel-type terminals accept 1 to 1.5 mm² rigid conductors (AWG 18 to 16), top or bottom, with a tightening torque of 0.8 N·m. IP20 finger protection per IEC 60529; IP40 in modular enclosure.

Listed under UL 489 and CSA C22.2 No 5, plus EN/IEC 60947-2 and GB 14048.2. Suitability for isolation per EN/IEC 60947-2. Lifecycle status: current production.

Durability and Service Life

Rated for 10,000 electrical cycles and 20,000 mechanical cycles. Padlockable toggle for lockout/tagout. Local ON/OFF indication on the toggle.

MPN