Skip to main content
Schneider Electric MGN61808 — 1-Pole MCB (DIN Rail)

MGN61808 Multi9 C60H-DC MCB, 1P, 32 A, Curve B, 20 kA DC

MPNMGN61808
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61808, 1-pole DC miniature circuit breaker, 32 A rated current, B curve, 20 kA breaking capacity at 110 V DC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61808 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H-DC
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN61808 — Electrical & Protection
ParameterValue
Rated current (In)32 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)250 V DC 110 V DC 220 V DC
Tripping curve codeB
Magnetic tripping limit5.5 x In +/- 20 % DC
Breaking capacity (Icu / AIR)20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN61808 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom)1...35 mm² (AWG 18...AWG 2) - rigid stranded Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)3.5 N.m top or bottom
MGN61808 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
MGN61808 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2
MGN61808 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V DC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric MGN61808 is a 1-pole DC miniature circuit breaker from the Multi9 C60H-DC series, rated 32 A at 50 °C with a B tripping curve. The thermal-magnetic trip unit protects DC circuits up to 250 V DC, with a magnetic trip threshold of 5.5 x In ±20% DC — meaning it clears short-circuit faults fast while riding through inrush on resistive or lightly inductive DC loads.

Breaking capacity and isolation

Rated Icu of 20 kA at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC per EN/IEC 60947-2. That 20 kA figure at the common 110 V DC bus voltage means it handles high fault currents on telecom or solar combiner outputs without cascading upstream.

Strip length 14 mm, tightening torque 3.5 N.m.

Frequently asked questions

Where can I buy MGN61808 and what is the lead time?

The MGN61808 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

What is the breaking capacity of MGN61808 at different DC voltages?

20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC, all per EN/IEC 60947-2. The 20 kA rating at 110 V DC is the key figure for most telecom and solar DC bus applications.

What compliance standards does MGN61808 meet?

Certified to EN/IEC 60947-2 for miniature circuit breakers. Pollution degree 3 per EN 60947-2, tropicalisation class 2 per IEC 60068-2. IP20 on terminals, IP40 on the modular enclosure.

MPN