Skip to main content
Schneider Electric MGN61872

MGN61872 Multi9 C60H-DC MCB, 40 A, 1P, K Curve, DC

MPN MGN61872
Obsolete

Schneider Electric Multi9 C60H-DC miniature circuit breaker, MGN61872, 1 pole, 40 A, K curve, DC network, breaking capacity 20 kA at 110 V DC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61872 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN 60947-2

All specifications

MGN61872 additional specifications
ParameterValue
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The MGN61872 is a Schneider Electric Multi9 C60H-DC miniature circuit breaker — a 1-pole, 40 A thermal-magnetic DC breaker with a K curve, designed for distribution applications on DC networks. Rated breaking capacity is 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC, all conforming to EN/IEC 60947-2. The K-curve magnetic tripping limit is 12 x In +/- 20 % DC, which means it trips magnetically between roughly 9.6 and 14.4 times rated current — suited for loads with moderate inrush, like DC motor circuits or battery-backed supplies. It carries IP20 protection on the terminals and IP40 on the modular enclosure, so it's intended for enclosed panel mounting, not washdown environments.

Terminal & Wiring Details

Tunnel-type terminals accept a wide range of conductors: 1 to 35 mm² rigid stranded (AWG 18 to AWG 2) for a single cable, or up to 3 x 4 mm² flexible stranded. The breaker is padlockable and has a toggle control with ON/OFF indication and a contact position indicator.