Skip to main content
Schneider Electric MGN61872 — 1-Pole MCB (DIN Rail)

MGN61872 Multi9 C60H-DC MCB, 40 A, 1P, K Curve, DC

MPNMGN61872
Obsolete

Schneider Electric Multi9 C60H-DC miniature circuit breaker, MGN61872, 1 pole, 40 A, K curve, DC network, breaking capacity 20 kA at 110 V DC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61872 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H-DC
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN61872 — Electrical & Protection
ParameterValue
Rated current (In)40 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)250 V DC 110 V DC 220 V DC
Tripping curve codeK
Magnetic tripping limit12 x In +/- 20 % DC
Breaking capacity (Icu / AIR)20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN61872 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom)1...35 mm² (AWG 18...AWG 2) - rigid stranded Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)3.5 N.m top or bottom
MGN61872 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
MGN61872 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2
MGN61872 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V DC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The MGN61872 is a Schneider Electric Multi9 C60H-DC miniature circuit breaker — a 1-pole, 40 A thermal-magnetic DC breaker with a K curve, designed for distribution applications on DC networks. Rated breaking capacity is 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC, all conforming to EN/IEC 60947-2. The K-curve magnetic tripping limit is 12 x In +/- 20 % DC, which means it trips magnetically between roughly 9.6 and 14.4 times rated current — suited for loads with moderate inrush, like DC motor circuits or battery-backed supplies. It carries IP20 protection on the terminals and IP40 on the modular enclosure, so it's intended for enclosed panel mounting, not washdown environments.

Terminal & Wiring Details

Tunnel-type terminals accept a wide range of conductors: 1 to 35 mm² rigid stranded (AWG 18 to AWG 2) for a single cable, or up to 3 x 4 mm² flexible stranded. The breaker is padlockable and has a toggle control with ON/OFF indication and a contact position indicator.

Frequently asked questions

What is MGN61872 used for?

The MGN61872 is a miniature circuit breaker for DC networks, rated 40 A with a K curve, used for distribution and protection of DC circuits such as battery banks, DC motor drives, or solar arrays.

Where can I buy MGN61872?

The MGN61872 is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of MGN61872?

The breaking capacity is 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC, all per EN/IEC 60947-2.

What standards does MGN61872 comply with?

The MGN61872 complies with EN/IEC 60947-2, pollution degree 3, and tropicalisation class 2 per IEC 60068-2.

MPN