Skip to main content
Schneider Electric MGN61874

Schneider Electric MGN61874 Multi9 C60H-DC MCB, 1P, 63 A, K-

MPN MGN61874
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61874, miniature circuit breaker, 1P, 63 A, K-curve, 20 kA Icu at 110 V DC, clip-on DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61874 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61874 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit breaker for distribution panels

The Schneider Electric MGN61874 is a Multi9 C60H-DC miniature circuit breaker rated 63 A at 50 °C per EN/IEC 60947-2, with a K-curve magnetic trip at 12 x In ±20 % DC. It is a single-pole (1P) DC-only breaker, clip-mounted on DIN rail, suited for DC distribution in control panels and sub-distribution boards where DC loads (battery banks, DC drives, telecom rectifiers) need overcurrent and short-circuit protection.

Breaking capacity and selectivity — what the ratings mean

Breaking capacity is rated 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC per EN/IEC 60947-2. For a 220 V DC bus (common in industrial DC link circuits), the 10 kA rating still covers most panel-fed loads; only a high-fault location (close to a large battery bank or rectifier) would need coordination upstream. The K-curve (12 x In magnetic trip) is designed for DC loads with moderate inrush — think DC contactors, solenoids, or resistive loads — not for high-inrush capacitive loads (which want a Z-curve) or purely resistive (B-curve).

Clip-on mounting on DIN rail, occupies 2 x 9 mm pitches (18 mm width). Tightening torque 3.5 N.m. IP20 finger-safe (IP40 in modular enclosure). Padlockable toggle for lockout/tagout. Pollution degree 3, tropicalisation class 2 per IEC 60068-2. Suitability for isolation confirmed per EN/IEC 60947-2.

MPN
MGN61874