Schneider Electric MGN61875 — 2-Pole MCB (DIN Rail)

MGN61875 Multi9 C60H-DC MCB, 1 A, Curve K, 2P DC, 20 kA

MPNMGN61875
Obsolete

Schneider Electric Multi9 C60H-DC, 1 A, 2-pole DC miniature circuit breaker, curve K, 20 kA breaking capacity at 220 V DC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61875 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Series / familyMulti9
Device short nameC60H-DC
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN61875 — Electrical
ParameterValue
Rated current [In]1 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]250 V DC 500 V DC 220 V DC 440 V DC
Network type (AC/DC)DC
MGN61875 — Protection
ParameterValue
Tripping curve codeK
Magnetic tripping limit12 x In +/- 20 % DC
Breaking capacity (Icu)20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN61875 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded
Terminal tightening torque2.5 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN61875 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
MGN61875 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

DC circuit breaker for distribution panels — 1 A, curve K, 2 poles

The MGN61875 is a 1 A, 2-pole DC miniature circuit breaker from the Schneider Electric Multi9 C60H-DC series. It uses a thermal-magnetic trip unit with a K curve, meaning the magnetic trip threshold is 12 x In (±20%) — designed to handle the inrush of DC loads like solenoids, relays, and control transformers without nuisance tripping. Rated for DC networks only, it carries a breaking capacity of 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC per EN/IEC 60947-2. That covers most industrial DC bus voltages up to 500 V DC. The 2-pole configuration protects both conductors in a DC circuit, with both poles switched and protected.

The 73 mm depth fits standard distribution board enclosures. IP20 finger-safe terminals; IP40 in the modular enclosure. Dual and triple cable entries are supported for daisy-chaining. Tropicalisation class 2 per IEC 60068-2 handles humidity up to 95% at 55 °C.

Frequently asked questions

What is the breaking capacity of MGN61875 at 220 V DC?

20 kA Icu at 220 V DC per EN/IEC 60947-2, with 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC.

What curve and trip threshold does MGN61875 use?

Curve K with a magnetic trip threshold of 12 x In (±20%), designed for DC loads with moderate inrush.

Where can I buy MGN61875?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance standards does MGN61875 meet?

Designed and tested to EN/IEC 60947-2 for circuit-breakers. Pollution degree 3, tropicalisation class 2, IP20/IP40 protection.