Schneider Electric MGN61883

Schneider MGN61883 Multi9 C60H-DC MCB, 2P, 13 A, Curve K, DC

MPN MGN61883
Obsolete

Schneider Electric Multi9 C60H-DC, miniature circuit breaker, 2P, 13 A, curve K, DC network, breaking capacity 20 kA at 250 V DC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61883 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 500 V DC 220 V DC 440 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61883 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric MGN61883 is a Multi9 C60H-DC miniature circuit breaker (MCB) rated 13 A at 50 °C with a K tripping curve, designed for DC networks.

This 2-pole breaker delivers 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2.

Curve K — why it matters for DC loads

The K curve trips magnetically at 12 x In (±20 %) — that is 156 A instantaneous for this 13 A unit. K-curve breakers are built for inductive loads (motors, transformers, solenoids) that draw a high inrush without nuisance tripping, while still providing short-circuit protection. On a DC network, the thermal-magnetic trip unit handles the sustained overload via the bimetal strip; the magnetic coil clears the hard faults.

Installation and wiring notes

Tunnel terminals accept 1 to 25 mm² rigid stranded (AWG 18 to AWG 4) or 1 to 16 mm² flexible with ferrule. Strip length 14 mm, tightening torque 2.5 N.m. IP20 finger-safe (IP40 in modular enclosure). Padlockable for lockout/tagout.

MPN
MGN61883