Skip to main content
Schneider Electric MGN61886

MGN61886 Multi9 C60H-DC MCB, 25 A, 2P, Curve K, 20 kA DC

MPN MGN61886
Obsolete

Schneider Electric Multi9 C60H-DC miniature circuit breaker, MGN61886, 25 A, 2-pole, curve K, 20 kA Icu at 250 V DC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61886 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 500 V DC 220 V DC 440 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61886 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit breaker for distribution panels

The MGN61886 is a Schneider Electric Multi9 C60H-DC miniature circuit breaker built for DC distribution. It's a 2-pole unit rated 25 A at 50°C with a K-curve trip characteristic — magnetic tripping at 12 x In ±20% DC. The real value here is the DC breaking capacity: 20 kA Icu at 250 V DC, 20 kA at 220 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2. That means it handles fault currents on DC bus systems up to 500 V, with the highest interruption rating at the more common 220–250 V DC levels.

The 2-pole configuration breaks both lines on a DC circuit, which is standard for ungrounded DC systems. The 500 V DC insulation voltage (Ui) confirms it's rated for the full voltage range, not just the lower end.

Height is 81 mm, depth 73 mm — fits standard distribution board cutouts. IP20 finger-safe terminals, IP40 in the modular enclosure. Tightening torque is 2.5 N.m. Padlockable for lockout/tagout. ON/OFF indicator on the toggle. Pollution degree 3 (industrial environment) per EN 60947-2.

MPN
MGN61886