Skip to main content
Schneider Electric MGN61886 — 2-Pole MCB (DIN Rail)

MGN61886 Multi9 C60H-DC MCB, 25 A, 2P, Curve K, 20 kA DC

MPNMGN61886
Obsolete

Schneider Electric Multi9 C60H-DC miniature circuit breaker, MGN61886, 25 A, 2-pole, curve K, 20 kA Icu at 250 V DC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61886 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Series / familyMulti9
Device short nameC60H-DC
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN61886 — Electrical
ParameterValue
Rated current [In]25 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]250 V DC 500 V DC 220 V DC 440 V DC
Network type (AC/DC)DC
MGN61886 — Protection
ParameterValue
Tripping curve codeK
Magnetic tripping limit12 x In +/- 20 % DC
Breaking capacity (Icu)20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN61886 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded
Terminal tightening torque2.5 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN61886 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
MGN61886 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

DC-rated miniature circuit breaker for distribution panels

The MGN61886 is a Schneider Electric Multi9 C60H-DC miniature circuit breaker built for DC distribution. It's a 2-pole unit rated 25 A at 50°C with a K-curve trip characteristic — magnetic tripping at 12 x In ±20% DC. The real value here is the DC breaking capacity: 20 kA Icu at 250 V DC, 20 kA at 220 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2. That means it handles fault currents on DC bus systems up to 500 V, with the highest interruption rating at the more common 220–250 V DC levels.

The 2-pole configuration breaks both lines on a DC circuit, which is standard for ungrounded DC systems. The 500 V DC insulation voltage (Ui) confirms it's rated for the full voltage range, not just the lower end.

Height is 81 mm, depth 73 mm — fits standard distribution board cutouts. IP20 finger-safe terminals, IP40 in the modular enclosure. Tightening torque is 2.5 N.m. Padlockable for lockout/tagout. ON/OFF indicator on the toggle. Pollution degree 3 (industrial environment) per EN 60947-2.

Frequently asked questions

Where can I buy MGN61886 and get current pricing?

The MGN61886 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of MGN61886 at different DC voltages?

The MGN61886 delivers 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2.

What compliance documentation does MGN61886 carry?

The MGN61886 is certified to EN/IEC 60947-2. It carries a pollution degree 3 rating and tropicalisation class 2 per IEC 60068-2. For specific RoHS/REACH/UL documentation, request the compliance package with your RFQ.

MPN
MGN61886