Skip to main content
Schneider Electric MGN61891

MGN61891 Multi9 C60H-DC MCB, 63 A, 2P, K Curve DC

MPN MGN61891
Obsolete

Schneider Multi9 C60H-DC, MGN61891, miniature circuit breaker, 2-pole, 63 A, K curve, DC network, breaking capacity 20 kA at 250 V DC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61891 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 500 V DC 220 V DC 440 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61891 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated MCB for photovoltaic and battery banks

The MGN61891 is a Schneider Multi9 C60H-DC miniature circuit breaker — a 2-pole, 63 A thermal-magnetic unit with a K curve, purpose-built for DC networks. It's rated 63 A at 50 °C per EN/IEC 60947-2, with a breaking capacity of 20 kA Icu at 250 V DC and 10 kA Icu at 440 V DC.

At 440 V DC the Icu drops to 10 kA, so verify your available fault current if you're using it on a 440 V battery bank. The K curve (12 x In magnetic trip) means it won't nuisance-trip on capacitor charging or motor inrush, but it's not for highly inductive loads — those need a Z curve.

Tunnel terminals accept up to 35 mm² rigid stranded or 25 mm² flexible — strip 14 mm, torque to 3.5 N·m. The IP20 finger-safe front and IP40 modular enclosure are standard for enclosed distribution boards. Padlockable toggle for lockout/tagout.

MPN
MGN61891