Schneider Electric MGN911524 — Residual Current Breakers (RCCB/RCBO)

MGN911524 RCBO, C Curve 20A 1P+N 4.5kA 30mA AC Type

MPNMGN911524
Obsolete

Schneider Electric Multi9 DPN Vigi RCBO, MGN911524, C curve 20A 1P+N 4.5kA 30mA AC type earth leakage, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN911524 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeClass AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
MGN911524 — Electrical Ratings
ParameterValue
Rated current (In)20 A at 30 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Device location in systemOutgoer
MGN911524 — Identification
ParameterValue
Product nameDPN Vigi
Product / component typeEarth leakage circuit breaker
Product range / familyMulti9
Device short nameDPNa Vigi-K
MGN911524 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
MGN911524 — Approvals
ParameterValue
StandardsGB 16917 IEC 61009-1

Product details

The MGN911524 is a Schneider Electric Multi9 DPN Vigi RCBO — a combined overcurrent and earth leakage protection device for single-phase outgoing circuits. It's rated 20 A at 30 °C with a C curve (magnetic trip 5...10 x In), 1P+N configuration, and 30 mA AC-type earth leakage sensitivity. Breaking capacity is 4.5 kA Icn at 230 V AC conforming to IEC 61009-1. The 30 mA sensitivity covers personnel protection against direct contact, and the AC-type detection handles sinusoidal residual currents typical of standard AC circuits. Mounts on DIN rail, neutral on the left, with toggle control and ON/OFF indication.

Listed to GB 16917 and IEC 61009-1, which covers the combined overcurrent and residual current device standard for household and similar installations. The AC-type earth leakage protection (Class AC) detects sinusoidal residual currents only — it's not rated for pulsed DC or smooth DC fault currents that might appear on VFD-fed or rectifier-fed circuits. For those applications, an A-type or B-type RCD would be needed.

Frequently asked questions

Where can I buy MGN911524 and how do I get a price?

MGN911524 is sourced through independent distribution as new-old-stock or verified surplus. Submit an RFQ for current availability and pricing — confirmed at quote time, not before.

What are the key ratings for MGN911524?

Rated 20 A at 30 °C, C curve (magnetic trip 5...10 x In), 1P+N, 4.5 kA breaking capacity at 230 V AC, 30 mA AC-type earth leakage sensitivity, instantaneous trip.

What standards does MGN911524 comply with?

It complies with GB 16917 and IEC 61009-1, and is suitable for isolation per IEC 60947-1.