Schneider Electric PowerPacT 4, Molded Case Circuit Breaker, 1P+N, 30 A at 40 °C, 230 V AC, TM-D trip unit, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP0302L3N — Identification
ParameterValue
Product / component typeCircuit breaker
Poles description1P + N
Device applicationDistribution
MGP0302L3N — Electrical & Protection
ParameterValue
Rated current (In)30 A at 40 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGP0302L3N — Mounting & Connection
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP0302L3N — Approvals
ParameterValue
Conformity standardsBS EN 60947-2
MGP0302L3N — Electrical
ParameterValue
[Ui] rated insulation voltage750 V
[Uimp] rated impulse withstand voltage8 kV

Product details

The MGP0302L3N is a Schneider Electric PowerPacT 4 molded case circuit breaker (MCCB) rated 30 A at 40 °C, 1P+N poles, 230 V AC 50/60 Hz operational voltage. It uses a thermal-magnetic TM-D trip unit with LI protection — L for thermal overload, I for magnetic short-circuit.

Ics is the same 25 kA, meaning it can also be reclosed after a fault at that level (service breaking capacity equals ultimate here). The 750 V rated insulation voltage (Ui) and 8 kV impulse withstand (Uimp) tell you it's built for distribution panels where transient overvoltages are expected. Backplate mounting with horizontal or vertical orientation gives flexibility in enclosure layout.

This is a distribution circuit breaker for panel-mounted installation — typically in a main or sub-feed distribution board protecting a branch circuit. The 1P+N configuration (switching line and neutral, protecting only the line) suits single-phase loads at 230 V AC. The 2-module width (35 mm per module) fits standard DIN-rail enclosures, though the mounting support is backplate, not snap-on DIN rail.

Frequently asked questions

What standard is MGP0302L3N certified to?

The MGP0302L3N is certified to BS EN 60947-2, the standard for low-voltage switchgear and controlgear — specifically for circuit breakers. It also carries suitability for isolation per that standard.

What is the breaking capacity of MGP0302L3N?

The MGP0302L3N has a 25 kA Icu (ultimate) and 25 kA Ics (service) short-circuit breaking capacity at 415 V AC 50/60 Hz. This means it can safely interrupt faults up to 25 kA and be reclosed after a fault at that level.

Where can I buy MGP0302L3N?

MGP0302L3N is sourced to order against an RFQ through independent industrial automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and delivery requirements.

MPN