MGP0632L1N PowerPacT 4 MCCB 1P+N 63A 230V AC, 25 kA Icu

MPNMGP0632L1N
Obsolete

Schneider Electric PowerPacT 4 series, MGP0632L1N Molded Case Circuit Breaker, 1P+N, 63 A at 40 °C, 230 V AC, 25 kA Icu at 415 V AC, TM-D trip unit, thermal-magnetic LI protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP0632L1N — Identification
ParameterValue
Product / component typeCircuit breaker
Poles description1P + N
Device applicationDistribution
MGP0632L1N — Electrical & Protection
ParameterValue
Rated current (In)63 A at 40 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGP0632L1N — Mounting & Connection
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP0632L1N — Approvals
ParameterValue
Conformity standardsBS EN 60947-2
MGP0632L1N — Electrical
ParameterValue
[Ui] rated insulation voltage750 V
[Uimp] rated impulse withstand voltage8 kV

Product details

The MGP0632L1N is a 1-pole-plus-neutral molded case circuit breaker from the PowerPacT 4 range, rated 63 A at 40 °C with a TM-D thermal-magnetic trip unit providing LI (overload and short-circuit) protection. It is designed for distribution in single-phase 230 V AC circuits (-N) and carries a 25 kA Icu and Ics at 415 V AC, with an 8 kV impulse withstand voltage. The breaker is panel-mounted, fits a 2-module 35 mm backplate, and can be installed horizontally or vertically.

The 25 kA Ics is the service breaking capacity, the level it can clear repeatedly; here it equals Icu, meaning the breaker can handle full-rated faults without derating for repeated operation. The 8 kV impulse withstand (Uimp) tells you it survives typical surge events in a 230/415 V distribution panel. The TM-D trip unit gives fixed thermal (L) and fixed magnetic (I) settings — no adjustment dials, so the 63 A is the only overload setting.

Durability and mechanicals

Rated for 20,000 electrical cycles at 277 V at rated current (In/2 gives 10,000 cycles at full load), and 20,000 mechanical cycles. The toggle control is manual; no shunt trip or auxiliary switch is built in. The breaker is 2 modules wide (35 mm per module) and mounts to a backplate — standard for panelboard or enclosure mounting.

Frequently asked questions

What is the closest alternative to MGP0632L1N?

No official successor order code has been published. Any replacement must be validated against the panel's coordination study and physical footprint — the PowerPacT 4 series has been superseded by newer ranges, but pin-compatible drop-in is not guaranteed.

What standards does MGP0632L1N comply with?

It complies with BS EN 60947-2, the standard for molded case circuit breakers, and is suitable for isolation per that standard.

What is the control type of MGP0632L1N?

The control type is Toggle — a manual switch handle on the front of the breaker.

Where can I buy MGP0632L1N?

We source MGP0632L1N to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
MGP0632L1N