Schneider Electric MGP0632L31 — 2-Pole MCB (DIN Rail)

MGP0632L31 PowerPacT 4 MCCB, 63A 2P 415V, Obsolete

MPNMGP0632L31
Obsolete

Schneider Electric PowerPacT 4, MGP0632L31, Molded Case Circuit Breaker, 2P, 63A at 40°C, 415V AC, 25kA Icu, BS EN 60947-2, TM-D trip unit, Obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP0632L31 — Identification
ParameterValue
Product rangePowerPacT 4
Product / component typeCircuit breaker
Device applicationDistribution
MGP0632L31 — Electrical
ParameterValue
Rated current [In]63 A at 40 °C
Pole configuration2P
Rated operational voltage [Ue]415 V AC 50/60 Hz
MGP0632L31 — Protection
ParameterValue
Suitable for isolationYes conforming to BS EN 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGP0632L31 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP0632L31 — Approvals
ParameterValue
Standards / complianceBS EN 60947-2

Product details

The MGP0632L31 is a Schneider Electric PowerPacT 4 molded case circuit breaker (MCCB) — 2-pole, 63 A at 40 °C, rated 415 V AC 50/60 Hz.

Above that temperature, thermal derating applies — a panel running at 50 °C will need a higher-rated frame or forced ventilation. The 8 kV impulse withstand voltage (Uimp) covers typical transient overvoltages in a 400 V class installation.

Integration Notes

Panel-mounted via backplate — not a DIN-rail snap-on, so plan for screw-fixed mounting in the enclosure. Accepts horizontal or vertical orientation, which helps in tight gland-plate layouts. The toggle control is manual; no motor operator or shunt trip is included, so remote tripping requires an external accessory. 2-module width (35 mm per module) on the backplate footprint.

Frequently asked questions

What are the key ratings of MGP0632L31?

63 A at 40 °C continuous, 2-pole, 415 V AC 50/60 Hz operational voltage, 25 kA Icu/Ics short-circuit breaking capacity at 415 V, with a TM-D thermal-magnetic trip unit providing LI (overload and short-circuit) protection. It is certified to BS EN 60947-2.

What standard does MGP0632L31 comply with?

It is certified to BS EN 60947-2, the harmonized European standard for low-voltage switchgear and controlgear — specifically for circuit breakers. It also carries a suitability-for-isolation declaration per that standard.

How do I get current pricing and availability for MGP0632L31?

Submit an RFQ against this order code. Because the part is obsolete, availability and price vary by lot; we confirm both at quote time through our independent sourcing network.

MPN
MGP0632L31