Skip to main content
Schneider Electric MGP0802L1N — 1-Pole MCB (DIN Rail)

MGP0802L1N PowerPacT 4 MCCB 80A 1P+N, Obsolete

MPNMGP0802L1N
Obsolete

Schneider Electric PowerPacT 4 molded case circuit breaker, MGP0802L1N, 1P+N, 80 A at 40 °C, 230 V AC, 25 kA Icu/Ics at 415 V, thermal-magnetic trip unit TM-D, BS EN 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP0802L1N — Identification
ParameterValue
Product / component typeCircuit breaker
Poles description1P + N
Device applicationDistribution
MGP0802L1N — Electrical & Protection
ParameterValue
Rated current (In)80 A at 40 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGP0802L1N — Mounting & Connection
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP0802L1N — Approvals
ParameterValue
Conformity standardsBS EN 60947-2
MGP0802L1N — Electrical
ParameterValue
[Ui] rated insulation voltage750 V
[Uimp] rated impulse withstand voltage8 kV

Product details

The MGP0802L1N is a Schneider Electric PowerPacT 4 molded case circuit breaker (MCCB) rated 80 A at 40 °C, 1P+N configuration, with a thermal-magnetic TM-D trip unit providing LI protection (overload and short-circuit). It is designed for distribution applications in panel-mounted backplate installations, horizontal or vertical orientation, and carries a 25 kA Icu and Ics at 415 V AC — meaning it can safely interrupt a fault up to that level and be reclosed at the same rating, which is useful for main or feeder duty where selectivity matters.

Lifecycle & sourcing

The manufacturer lists the MGP0802L1N as obsolete. No official successor order code is provided in the record. For a BOM line or installed base that needs this exact part, the sourcing path is through independent distribution — quoted to order against an RFQ, with availability and current pricing confirmed at quote time.

Frequently asked questions

What is MGP0802L1N's short-circuit breaking capacity?

The MGP0802L1N has a rated ultimate short-circuit breaking capacity (Icu) of 25 kA at 415 V AC 50/60 Hz, and the same 25 kA for the service breaking capacity (Ics) at that voltage. At 230 V AC the values are the same.

What standards does MGP0802L1N comply with?

It is certified to BS EN 60947-2, the standard for low-voltage switchgear and controlgear — circuit breakers. It is also suitable for isolation per that standard.

Where can I buy the MGP0802L1N?

The MGP0802L1N is obsolete but can be sourced through independent distribution. Submit an RFQ for current availability and pricing; it is quoted to order.

MPN
MGP0802L1N