Skip to main content
Schneider Electric MGP1252L23 — 2-Pole MCB (DIN Rail)

Schneider Electric MGP1252L23 PowerPacT 4 MCCB, 125A, 25kA

MPNMGP1252L23
Obsolete

Schneider Electric PowerPacT 4 series, MGP1252L23, molded case circuit breaker, 2-pole, 125A, 415V AC, 25kA Icu/Ics, thermal-magnetic TM-D trip unit, LI protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP1252L23 — Identification
ParameterValue
Product rangePowerPacT 4
Product / component typeCircuit breaker
Device applicationDistribution
MGP1252L23 — Electrical
ParameterValue
Rated current [In]125 A at 40 °C
Pole configuration2P
Rated operational voltage [Ue]415 V AC 50/60 Hz
MGP1252L23 — Protection
ParameterValue
Suitable for isolationYes conforming to BS EN 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGP1252L23 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP1252L23 — Approvals
ParameterValue
Standards / complianceBS EN 60947-2

Product details

The MGP1252L23 is a 2-pole molded case circuit breaker from the Schneider Electric PowerPacT 4 range, rated 125 A at 40 °C with a TM-D thermal-magnetic trip unit providing LI protection — thermal overload (L) and magnetic short-circuit (I). It is certified to BS EN 60947-2, with an isolation suitability declaration conforming to that standard.

Lifecycle status

This part is classified as obsolete by the manufacturer. No official successor order code has been published for the MGP1252L23.

Mounting and application context

Panel-mounted via backplate, accepting horizontal or vertical orientation. The 2-module 35 mm footprint suits standard enclosure backplate layouts. Phase connection is L2-L3, making this breaker specific to two-pole distribution circuits — not a three-phase main. Electrical durability is 20,000 cycles at rated current and 10,000 cycles at 2× In, both at 277 V; mechanical durability matches at 20,000 cycles.

Frequently asked questions

What is the breaking capacity of MGP1252L23?

Both Icu and Ics are 25 kA at 415 V AC 50/60 Hz, giving symmetrical fault interruption without service derating.

What standards does MGP1252L23 comply with?

It is certified to BS EN 60947-2 and declared suitable for isolation per that standard.

Where can I buy MGP1252L23?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
MGP1252L23