Skip to main content
Schneider Electric MGP1252L2N — 1-Pole MCB (DIN Rail)

MGP1252L2N PowerPacT 4 MCCB, 125A, 25kA, Obsolete

MPNMGP1252L2N
Obsolete

Schneider Electric PowerPacT 4, Molded Case Circuit Breaker, 1P+N, 125A, 230V AC, TM-D trip unit, BS EN 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP1252L2N — Identification
ParameterValue
Product / component typeCircuit breaker
Poles description1P + N
Device applicationDistribution
MGP1252L2N — Electrical & Protection
ParameterValue
Rated current (In)125 A at 40 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGP1252L2N — Mounting & Connection
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP1252L2N — Approvals
ParameterValue
Conformity standardsBS EN 60947-2
MGP1252L2N — Electrical
ParameterValue
[Ui] rated insulation voltage750 V
[Uimp] rated impulse withstand voltage8 kV

Product details

The MGP1252L2N is a 1-pole-plus-neutral (1P+N) molded case circuit breaker from the Schneider Electric PowerPacT 4 range, rated 125 A at 40 °C with a TM-D thermal-magnetic trip unit providing LI (overload and short-circuit) protection. It is designed for distribution applications on 230 V AC 50/60 Hz circuits, with a 25 kA Icu / Ics short-circuit breaking capacity at 415 V AC — meaning it can safely interrupt a fault up to that level without upstream gear having to clear it. The breaker mounts to a backplate in either horizontal or vertical orientation, and its suitability for isolation is certified per BS EN 60947-2 — a requirement in many European panel specs.

Schneider Electric has marked the MGP1252L2N as obsolete. There is no official successor order code listed, so a direct drop-in replacement from the PowerPacT 4 family is not confirmed. The 25 kA Icu at 415 V and 125 A rating are the specs to match if you are looking for a functional equivalent.

Above that, the thermal curve starts its time-delayed overload response. The magnetic (I) element is fixed-trip, not adjustable — it responds to short-circuit currents without intentional delay. Rated insulation voltage is 750 V and impulse withstand is 8 kV, which covers the clearance and creepage requirements for 230/415 V systems. The electrical durability is 20,000 cycles at rated current at 277 V, dropping to 10,000 cycles at 2x In — typical for a distribution MCCB not cycled as a motor switch.

Frequently asked questions

What is the breaking capacity of MGP1252L2N?

The MGP1252L2N has a 25 kA Icu and 25 kA Ics short-circuit breaking capacity at 415 V AC 50/60 Hz, per BS EN 60947-2.

What standard does MGP1252L2N comply with?

It complies with BS EN 60947-2, the standard for low-voltage switchgear and controlgear circuit breakers.

Where can I buy MGP1252L2N?

This obsolete MCCB is available through independent distribution channels. Submit an RFQ for a quote — availability and current pricing are confirmed at quote time.

MPN
MGP1252L2N