Schneider Electric MGP1601L3 — 1-Pole MCB (DIN Rail)

MGP1601L3 PowerPacT 4 MCCB, 160A, 1P, 25kA at 230V

MPNMGP1601L3
Obsolete

Schneider Electric PowerPacT 4, MGP1601L3, 1-pole molded case circuit breaker, 160 A, 230 V AC, 25 kA breaking capacity, TM-D trip unit, panel-mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP1601L3 — Identification
ParameterValue
Product / component typeCircuit breaker
Poles description1P
Device applicationDistribution
MGP1601L3 — Electrical & Protection
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGP1601L3 — Mounting & Connection
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP1601L3 — Approvals
ParameterValue
Conformity standardsBS EN 60947-2
MGP1601L3 — Electrical
ParameterValue
[Ui] rated insulation voltage750 V
[Uimp] rated impulse withstand voltage8 kV

Product details

The Schneider Electric MGP1601L3 is a 1-pole PowerPacT 4 molded case circuit breaker (MCCB) rated 160 A at 40 °C, for 230 V AC 50/60 Hz distribution circuits.

This part is officially obsolete per the manufacturer. There is no listed direct successor order code.

Rated 160 A thermal-magnetic, fixed — no adjustable thermal or magnetic pickup, so the trip curve is fixed by the TM-D unit. The 25 kA Icu at 230 V AC matches the service short-circuit rating (Ics), meaning the breaker can be reclosed after a fault at that level. Rated insulation voltage is 750 V, impulse withstand 8 kV, so it's suitable for standard 230 V distribution panels with adequate clearance. Mechanical durability is 20,000 cycles; electrical durability is 20,000 cycles at rated current and 10,000 at 2x In, which is typical for a distribution-grade MCCB.

Panel-mounted on a backplate, with horizontal or vertical orientation allowed. It occupies one 35 mm module width. The toggle control is the manual on/off actuator.

Frequently asked questions

What is the breaking capacity of MGP1601L3?

The MGP1601L3 has a 25 kA ultimate (Icu) and service (Ics) short-circuit breaking capacity at 230 V AC 50/60 Hz.

What standard does MGP1601L3 comply with?

The MGP1601L3 complies with BS EN 60947-2, the standard for low-voltage switchgear and controlgear circuit breakers.

Where can I buy MGP1601L3?

The MGP1601L3 is obsolete but available to source through independent distribution. Submit an RFQ for current pricing and availability.

MPN