Specifications

MGP2504XFO — Identification
ParameterValue
Product range (series)PowerPacT 4
Product/component typeBasic frame
Device applicationDistribution
MGP2504XFO — Ratings
ParameterValue
Rated current (In)250 A
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V
Rated impulse withstand voltage (Uimp)8 kV
Utilisation categoryCategory A
MGP2504XFO — Protection
ParameterValue
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
MGP2504XFO — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Contact position indicatorYes
Width140 mm
Height161 mm
Depth86 mm
MGP2504XFO — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to EN/IEC 60529
Pollution degree3 conforming to EN/IEC 60664-1
MGP2504XFO — Approvals
ParameterValue
StandardsBS EN 60947-2
MGP2504XFO — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity50 kA at 415 V AC 50/60 Hz

Product details

The MGP2504XFO is a PowerPacT 4 basic frame — a 250 A, 4-pole panel-mounted breaker frame rated 50 kA Icu and Ics at 415 V AC 50/60 Hz, with an 800 V rated insulation voltage and 8 kV impulse withstand. It ships without a trip unit, so you add the appropriate thermal-magnetic or electronic trip block separately. Designed for distribution in 250 A or 400/630 A panelboards, it meets BS EN 60947-2 and carries a Category A utilization rating, meaning it's intended for non-discriminative (non-selective) coordination — downstream faults clear it, but it doesn't guarantee selectivity with series devices.