Skip to main content
Schneider Electric SR3XT141FU

Schneider Electric SR3XT141FU Zelio Logic Extension Module,

MPNSR3XT141FU
Active

Schneider Electric Zelio Logic, SR3XT141FU, discrete I/O extension module, 8 inputs 100-240 V AC, 85-264 V AC supply, IP20/IP40.

$50.80Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

SR3XT141FU key specifications
ParameterValue
Range of productZelio Logic
Product or component typeDiscrete I/O extension module
Supply voltage limits85...264 V
Discrete input voltage100...240 V AC
Supply voltage100...240 V AC
Voltage state 0 guaranteed= 0.17 mA discrete input)
Voltage state 1 guaranteed>= 79 V discrete input
[Uimp] rated impulse withstand voltage4 kV EN/IEC 60947-1 and EN/IEC 60664-1
Discrete input current0.6 mA
Current state 0 guaranteed= 10 mA 12 V relay output)
Supply frequency50/60 Hz
Operating rate in0.1 Hz at Ie)relay output 10 Hz no load)relay output

All specifications

SR3XT141FU additional specifications
ParameterValue
Discrete input frequency57...63 Hz 47...53 Hz
IP degree of protectionIP20 IEC 60529 terminal block) IP40 IEC 60529 front panel)
Connections - terminalsScrew terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid
Response time50 ms ladder from state 0 to state 1)discrete input 50 ms ladder from state 1 to state 0)discrete input 50...255 ms FBD from state 0 to state 1)discrete input 50...255 ms FBD from state 1 to state 0)discrete input 10 ms from state 0 to state 1)relay output 5 ms from state 1 to state 0)relay output
Pollution degree2 IEC 61131-2
Relative humidity95 % without condensation or dripping water
Operating altitude6561.68 ft (2000 m)
Maximum altitude transport10000 ft (3048 m)
Mechanical durability10000000 cycles relay output
StandardsIEC 61000-4-6 level 3 IEC 61000-4-2 level 3 IEC 61000-4-4 level 3 IEC 60068-2-27 Ea IEC 61000-4-5 IEC 61000-4-11 IEC 60068-2-6 Fc IEC 61000-4-12 IEC 61000-4-3
ChecksProgram memory on each power up
CategoryUS1000I22378
Cycle time6...90 ms
Backup time10 years 77 °F (25 °C)
Clock drift12 min/year 32...131 °F (0...55 °C)
Tightening torque4.4 lbf.in (0.5 N.m)
Overvoltage categoryIII conforming to IEC 60664-1
Discrete input number8
Reverse polarity protectionWith
Environmental characteristicEMC directive conforming to IEC 61000-6-2 EMC directive conforming to IEC 61000-6-3 EMC directive conforming to IEC 61000-6-4 EMC directive conforming to IEC 61131-2 zone B Low voltage directive conforming to IEC 61131-2
Disturbance radiated (conducted)Class B EN 55022-11 group 1
Number or control scheme lines120 ladder
Ambient air temperature for storage-40...158 °F (-40...70 °C)
Ambient air temperature for operation-4...104 °F (-20...40 °C) in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 -4...131 °F (-20...55 °C) IEC 60068-2-1 and IEC 60068-2-2

Product details

The SR3XT141FU: Cycle time sits at 6-90 ms for the ladder logic engine, and discrete input response from state 0 to state 1 is 50 ms (ladder) or 50-255 ms (FBD). Relay output response: 10 ms to close, 5 ms to open. That spec is consistent with the Zelio family's typical scan rates for slow to moderate process I/O.

The screw terminals accept 0.2-2.5 mm² solid or 0.25-1.5 mm² flexible (ferruled) wire, with a tightening torque of 0.5 N·m. IP20 at the terminal block, IP40 at the front panel. Storage from -40 to 70 °C. Pollution degree 2 per IEC 61131-2; overvoltage category III. Altitude limit 2000 m operating, 3048 m transport.

Compliance and immunity

The SR3XT141FU carries IEC 61000-4-2/3/4/5/6/11/12 at level 3, plus IEC 60068-2-6 and 2-27 vibration and shock. Radiated and conducted emissions meet Class B per EN 55022-11 group 1. The low-voltage directive and EMC directives (IEC 61000-6-2, -3, -4) are cited. For procurement, this means the module is accepted in CE-marked panels without additional filtering for most light-industrial environments. Backup time for the real-time clock is 10 years at 25 °C; clock drift is 12 min/year over 0-55 °C. That clock holds time and date through power cycles as long as the internal battery is fresh.

Sourcing posture

Lifecycle stage is flagged as current production. No EOL or PCN is indicated in the record. Supply is steady through the standard Schneider distribution channel; orders placed against an RFQ will fill without allocation risk for the foreseeable future. If you are substituting into a legacy design, confirm the firmware compatibility with the base CPU revision — the module is functionally identical to earlier SR3XT141 variants but the bus protocol may differ between Zelio Logic generations.

Frequently asked questions

What compliance documentation does the SR3XT141FU carry?

It conforms to IEC 61000-4-2/3/4/5/6/11/12 level 3, IEC 60068-2-27/2-6, EN 55022-11 Class B, and the Low Voltage Directive per IEC 61131-2. The EMC directives IEC 61000-6-2, -3, -4 are also cited.

What does 'Checks Program memory on each power up' mean for this module?

It means the module performs a self-test of its program memory integrity every time power is applied. This is a diagnostic routine common in safety-conscious designs; if memory corruption is detected, the module will flag an error rather than execute faulty logic.

MPN
SR3XT141FU