Skip to main content
Schneider Electric TA10D3S0404TPE — Miniature Circuit Breakers (MCB)

Schneider Electric TA10D3S0404TPE TransferPacT ATS, 40A, 3P,

MPNTA10D3S0404TPE
Active

Schneider Electric TransferPacT automatic, TA10D3S0404TPE, automatic transfer switch, 40 A, 3 poles, 400 V AC, rotary selector control, PC class per IEC 60947-6-1.

$982.19Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

TA10D3S0404TPE — Identification
ParameterValue
Product range (series)TransferPacT
Product/component typeAutomatic transfer switch
Device applicationChange source of supply
TA10D3S0404TPE — Ratings
ParameterValue
Poles configuration3P
Rated operational voltage (Ue)400 V AC 50/60 Hz
Rated insulation voltage (Ui)Switch: 800 V Controller: 500 V
Rated impulse withstand voltage (Uimp)Switch: 6 kV Controller: 6 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
TA10D3S0404TPE — Protection
ParameterValue
Suitability for isolationYes
Mechanical durability (cycles)8000 cycles
TA10D3S0404TPE — Mechanical
ParameterValue
Mounting supportPlate DIN rail
Mounting modeFixed
Control typeRotary knob Selector switch
Contact position indicatorYes
Width310 mm
Height147 mm
Depth94 mm
TA10D3S0404TPE — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionFront face: IP40 auto mode Inside the enclosure: IP20 manual mode
Pollution degree3
TA10D3S0404TPE — Approvals
ParameterValue
StandardsIEC 60947-6-1

Product details

TransferPacT TA10D3S0404TPE — 40 A automatic transfer switch for source-changeover duty

It is classified as a PC-class transfer switch per IEC 60947-6-1, meaning it is a switching device that transfers the load between two sources but does not provide overcurrent protection — that is handled upstream by a circuit breaker or fuses. The utilization category AC-33B confirms it is suited for mixed resistive and motor loads, including motors up to 15 A inrush, plus tungsten and discharge lighting loads.

The short-time withstand current (Icw) is 5 kA for 0.1 s, which governs coordination with the upstream protective device: the switch must see the fault cleared within that window. Short-circuit making capacity (Icm) is 15 kA for the switch-disconnector alone at 400 V AC, rising to 75 kA with an upstream protection circuit breaker — the breaker must be selected to limit the let-through energy to what the switch can survive. Mechanical interlocking between the normal and emergency-source contacts is built in, preventing both sources from closing simultaneously. The switch offers three contact positions: ON (source 1), OFF, and ON (source 2). Signal contacts are configurable as 1 NO + 2 NC, 1 NC + 2 NO, or 2 NO — the buyer should confirm the factory configuration for their order. Mounting is by plate or DIN rail; connection pitch is 18 mm. Mechanical durability is 8000 cycles — for a transfer switch that typically operates only during a source failure or test, this is a long service life.

Frequently asked questions

Where can I buy the TA10D3S0404TPE and what is the lead time?

The TA10D3S0404TPE is sourced and quoted to order against an RFQ through independent distribution. Availability and current lead time are confirmed at quote time — submit an RFQ for a firm delivery commitment.

What is the closest alternative to the TA10D3S0404TPE in the TransferPacT family?

Within the TransferPacT automatic series, the closest alternative would be a different frame size or pole configuration — for example, a 63 A or 100 A variant if the load grows, or a 4-pole version for three-phase-plus-neutral systems. The PC class and AC-33B utilization category are consistent across the range. No pin-compatible drop-in exists; the frame size and connection pitch differ with the current rating.

What compliance documentation does Schneider provide for the TA10D3S0404TPE?

The TA10D3S0404TPE is designed and tested to IEC 60947-6-1. Standard documentation includes the product datasheet, installation manual, and IEC declaration of conformity. For specific RoHS, REACH, or UL documentation, confirm at quote time — these are typically available on request from the manufacturer or distributor.

MPN
TA10D3S0404TPE