Skip to main content
Schneider Electric TA10D4S0634TPE — Miniature Circuit Breakers (MCB)

Schneider Electric TA10D4S0634TPE TransferPacT ATS, 63A 4P,

MPNTA10D4S0634TPE
Active

Schneider Electric TransferPacT automatic, automatic transfer switch, 63 A, 4P, rotary selector, PC class per IEC 60947-6-1, 400 V AC 50/60 Hz.

$671.73 – $1,042.08Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

TA10D4S0634TPE — Identification
ParameterValue
Product range (series)TransferPacT
Product/component typeAutomatic transfer switch
Device applicationChange source of supply
TA10D4S0634TPE — Ratings
ParameterValue
Poles configuration4P
Rated operational voltage (Ue)400 V AC 50/60 Hz
Rated insulation voltage (Ui)Switch: 800 V Controller: 500 V
Rated impulse withstand voltage (Uimp)Switch: 6 kV Controller: 6 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
TA10D4S0634TPE — Protection
ParameterValue
Suitability for isolationYes
Mechanical durability (cycles)8000 cycles
TA10D4S0634TPE — Mechanical
ParameterValue
Mounting supportPlate DIN rail
Mounting modeFixed
Control typeRotary knob Selector switch
Contact position indicatorYes
Width310 mm
Height147 mm
Depth94 mm
TA10D4S0634TPE — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionFront face: IP40 auto mode Inside the enclosure: IP20 manual mode
Pollution degree3
TA10D4S0634TPE — Approvals
ParameterValue
StandardsIEC 60947-6-1

Product details

The Schneider Electric TA10D4S0634TPE is an automatic transfer switch (ATS) from the TransferPacT range, designed to change the source of supply between a normal and a backup power feed — typically a mains-to-generator or mains-to-mains transfer in a low-voltage distribution board. Rated 63 A continuous at 400 V AC 50/60 Hz across 4 poles (4P), it is classed as a PC transfer switch per IEC 60947-6-1, meaning it can make, carry, and break currents under normal and overload conditions but does not provide short-circuit protection — that is left to an upstream circuit breaker. The AC-33B utilization category confirms it handles mixed resistive and motor loads up to 63 A, which covers most lighting, heating, and small motor circuits in a commercial or light industrial backup scheme. Duty is uninterrupted (continuous), so no de-rating for extended run times — the switch stays closed on the preferred source indefinitely, only opening to transfer when the controller detects a loss or restoration of supply.

Short-circuit making capacity (Icm) is 15 kA peak at 400 V AC with the switch-disconnector alone, and 75 kA peak when an upstream circuit breaker coordinates — the breaker must be selected to limit let-through energy to protect the ATS. Rated short-time withstand current (Icw) is 5 kA for 0.1 s, which covers the time delay before the upstream breaker clears a fault — enough for a typical coordination study with a moulded-case breaker. Mechanical interlocking between the normal and standby contacts ensures both sources cannot be closed simultaneously, which is a safety requirement for paralleled supplies.

Connection pitch is 18 mm, and both upside and downside connections are screwed terminals — expect to terminate with ring or fork lugs for the 63 A rating. Control is via a rotary knob selector switch for Auto/Manual operation, and the switch includes a padlockable OFF position for lockout/tagout.

Frequently asked questions

What standard does the TA10D4S0634TPE comply with?

It complies with IEC 60947-6-1 as a PC class transfer switch, with AC-33B utilization category for mixed resistive and motor loads.

What are the mounting dimensions of this transfer switch?

Width 310 mm, height 147 mm, depth 94 mm. It mounts on a plate or DIN rail with 18 mm connection pitch.

MPN
TA10D4S0634TPE