Skip to main content
Schneider Electric TA16D4S0804TPE — Miniature Circuit Breakers (MCB)

Schneider TA16D4S0804TPE TransferPacT ATS, 80A, 4P, PC class

MPNTA16D4S0804TPE
Active

Schneider Electric TransferPacT automatic, automatic transfer switch, 80 A, 4 poles, PC class per IEC 60947-6-1, rotary selector, frame 160 A.

$848.89 – $2,535.84Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

TA16D4S0804TPE — Identification
ParameterValue
Product range (series)TransferPacT
Product/component typeAutomatic transfer switch
Device applicationChange source of supply
TA16D4S0804TPE — Ratings
ParameterValue
Poles configuration4P
Rated operational voltage (Ue)400 V AC 50/60 Hz
Rated insulation voltage (Ui)Switch: 800 V Controller: 500 V
Rated impulse withstand voltage (Uimp)Switch: 8 kV Controller: 6 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
TA16D4S0804TPE — Protection
ParameterValue
Suitability for isolationYes
Mechanical durability (cycles)10000 cycles
TA16D4S0804TPE — Mechanical
ParameterValue
Mounting supportPlate DIN rail
Mounting modeFixed
Control typeRotary knob Selector switch
Contact position indicatorYes
Width351 mm
Height164 mm
Depth95 mm
TA16D4S0804TPE — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionFront face: IP40 auto mode Inside the enclosure: IP20 manual mode
Pollution degree3
TA16D4S0804TPE — Approvals
ParameterValue
StandardsIEC 60947-6-1

Product details

The Schneider Electric TA16D4S0804TPE is a TransferPacT automatic transfer switch (ATS) rated 80 A continuous with four poles, built to the PC class standard per IEC 60947-6-1. That PC rating means the switch is intended for open-transition transfer of sources — it makes and breaks load current but is not listed for fault making and breaking like a circuit breaker.

The 80 A uninterrupted rating (Ith 80 A at 60 °C) sets the continuous current capacity in free air. For a transfer switch, this is the number that decides conductor sizing and upstream protection coordination — not a peak or inrush figure. The short-time withstand Icw is 10 kA for 0.1 s, meaning the switch can ride through a fault of that magnitude while upstream protection clears it. The mechanical interlocking between sources is built in, so both line and generator feeds can never close simultaneously. That is the core safety function of any ATS, and here it is backed by a mechanical durability rating of 10,000 cycles — enough for years of weekly generator tests in a commercial or light-industrial installation.

Mounts to a plate or DIN rail with a fixed footprint: 351 mm wide, 164 mm tall, 95 mm deep. Connection pitch is 30 mm, and both line and load terminations are screwed type — expect to torque per the nameplate values. The front face is IP40 in auto mode (tools required to access the selector), and inside the enclosure the live parts are IP20 in manual mode, which is standard for panel-mounted gear.

This part is current production — no end-of-life notice.

Frequently asked questions

What does the PC class mean on this transfer switch?

PC class per IEC 60947-6-1 means the switch is rated for making and breaking load currents but not for interrupting fault currents — it relies on upstream overcurrent protection to clear a short circuit. This is the standard class for most automatic transfer switches in commercial and industrial source-transfer applications.

What is TA16D4S0804TPE's depth and width for panel layout?

The TA16D4S0804TPE measures 95 mm deep and 351 mm wide, with a height of 164 mm. Mounting support is plate or DIN rail, with a 30 mm connection pitch.

MPN
TA16D4S0804TPE