| Voltage state 0 guaranteed | <= 5 V for input |
|---|
| Voltage state 1 guaranteed | >= 15 V for input |
|---|
| Inrush current | 50 A |
|---|
| Discrete input current | 7 mA for input 7 mA for fast input 9 mA for high speed input |
|---|
| Discrete output current | 2 A for relay output |
|---|
| Maximum current per output common | 4 A at COM 2 4 A at COM 0 4 A at COM 1 |
|---|
| Sensor power supply | 24 V DC at 300 mA supplied by the controller |
|---|
| Power consumption in | 55...66 VA at 100...240 V AC (with max I/O) |
|---|
| Network frequency | 50/60 Hz |
|---|
| Switching frequency | 0.1 Hz with maximum load |
|---|
| IP degree of protection | IP20 with protective cover in place |
|---|
| Communication port protocol | USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network |
|---|
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715 |
|---|
| Electrical connection | Mini B USB 2.0 connectorfor a programming terminal removable screw terminal blockfor inputs removable screw terminal blockfor outputs removable screw terminal block, 4 terminal(s) for connecting the serial link1 removable screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supply |
|---|
| Maximum cable distance between devices | Unshielded cable: Shielded cable: Shielded cable: Unshielded cable: <150 m for output |
|---|
| Response time | 10 ms turn-on, Q0...Q11 terminal(s) for output 10 ms turn-off, Q0...Q11 terminal(s) for output 5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input 100 µs turn-off, I2...I5 terminal(s) for fast input 35 µs turn-on, I2...I5 terminal(s) for fast input 100 µs turn-off, I8...I13 terminal(s) for regular input 35 µs turn-on, I8...I13 terminal(s) for regular input 125 µs turn-off, I14...I19 terminal(s) for regular input 55 µs turn-on, I14...I19 terminal(s) for regular input |
|---|
| Pollution degree | <= 2 |
|---|
| Shock resistance | 15 gn for 11 ms 30 gn for 6 ms |
|---|
| Storage altitude | 0...3000 m |
|---|
| Relative humidity | 10...95 %, without condensation (in operation) 10...95 %, without condensation (in storage) |
|---|
| Operating altitude | 0...2000 m |
|---|
| Vibration resistance | 3.5 mm at 5...8.4 Hz on symmetrical rail 1 gn at 8.4...150 Hz on symmetrical rail 3.5 mm at 5...8.7 Hz on panel mounting 2 gn at 8.7...150 Hz on panel mounting |
|---|
| Depth | 70 mm |
|---|
| Width | 175 mm |
|---|
| Height | 90 mm |
|---|
| Electrical durability | 100000 cycles AC-12, 240 V, 480 VA, resistive 100000 cycles DC-12, 24 V, 48 W, resistive |
|---|
| Mechanical durability | 20000000 cycles for relay output |
|---|
| Standards | IEC 61131-2 IEC 61010-2-201 |
|---|
| Marking | CE |
|---|
| Insulation | Non-insulated between inputs Between output and internal logic at 1780 V AC Between output groups at 1780 V AC Between supply and internal logic at 1780 V AC Between input and internal logic at 500 V AC Between fast input and internal logic at 500 V AC Between input groups at 500 V AC |
|---|
| Backup time | 3 years at 25 °C (by interruption of power supply) |
|---|
| Clock drift | <= 90 s/month at 25 °C |
|---|
| Minimum load | 10 mA at 5 V DC for relay output |
|---|
| Input impedance | 3.3 kOhm for discrete input |
|---|
| Memory capacity | 512 byte internal flash for backup of programs |
|---|
| Regulation loop | Adjustable PID regulator up to 14 simultaneous loops |
|---|
| Local signalling | 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED per channel (green) for I/O state |
|---|
| Transmission rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 12 Mbit/s for USB |
|---|
| Discrete i (O number) | 32 |
|---|
| Discrete input logic | Sink or source (positive/negative) type 1 conforming to IEC 61131-2 |
|---|
| Counting input number | 4 fast input (HSC mode) at 100 kHz 32 bits |
|---|
| Discrete input number | I2...I5: 4 fast input I0, I1, I6, I7: 4 high speed input I8...I19: 12 regular input |
|---|
| Data storage equipment | 32 GB micro SD card (optional) |
|---|
| Discrete output number | 12 relay |
|---|
| Immunity to microbreaks | 10 ms |
|---|
| Exct time for event task | 60 µs response time |
|---|
| Configurable filtering time | 0 ms for input 3 ms for input 12 ms for input |
|---|
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m (80 MHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to IEC 55011 Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to IEC 55011 |
|---|
| Execution time per instruction | 0.2 µs Boolean |
|---|
| Execution time for 1 KInstruction | 0.3 ms for event and periodic task |
|---|
| Ambient air temperature for storage | -25...70 °C |
|---|
| Ambient air temperature for operation | 0...55 °C (horizontal installation) |
|---|