Skip to main content
Schneider Electric TM2ARI8LRJ

Schneider TM2ARI8LRJ 8-Channel RTD Module, Obsolete

MPNTM2ARI8LRJ
Obsolete

Schneider Modicon M238 analog input module, 8-channel RTD, TM2ARI8LRJ, Pt100/Pt1000, 12-bit resolution, 24 V DC supply.

$699.49Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

TM2ARI8LRJ key specifications
ParameterValue
Range of productModicon M238 logic controller
Analogue input typePt 100 temperature probe - 200...600 °C non differential Pt 1000 temperature probe - 50...200 °C non differential
Product or component typeAnalog input module
Supply voltage limits19.2...30 V
Supply voltage24 V DC
Current consumption90 mA 5 V DC internal
Electrical connection1 removable screw terminal block power supply 8 connectors RJ11 sensors
Depth2.8 in (70 mm)
Width1.5 in (39.1 mm)
Height3.5 in (90 mm)
SupplyExternal supply
Category22531-PLCS, TWIDO, TWD

All specifications

TM2ARI8LRJ additional specifications
ParameterValue
LSB value0.006 °C Pt 1000 0.2 °C Pt 100
Total error1 °C Pt 1000 4 °C Pt 100
Input impedance>= 10 kOhm
Repeat accuracy+/- 0.1 °C
Measurement error+/- 0.3 % of full scale Pt 1000 25 °C +/- 0.5 % of full scale Pt 100 25 °C
Sampling duration160 ms
Acquisition period320 ms per group of channel + 1 controller cycle time
Dielectric strength500 V between the I/O and the external supply circuit 2500 V between the I/O and internal logic
Analogue input number8
Temperature coefficient+/-0.01 %FS/°C
Analogue input resolution12 bits
Insulation between channel and internal logicPhotocoupler

Product details

8-Channel RTD Input Module

The Schneider TM2ARI8LRJ is an 8-channel analog input module for the Modicon M238 logic controller, now obsolete. Reads Pt100 probes from -200 to 600 °C and Pt1000 from -50 to 200 °C, both non-differential, with 12-bit resolution and a total error of 1 °C (Pt1000) or 4 °C (Pt100). Sampling takes 160 ms per channel; acquisition runs 320 ms per group plus one controller cycle.

Panel Integration

Mounts on the M238 backplane; draws 90 mA from the 5 V DC rail. External supply needed: 19.2…30 V DC (rated 24 V DC). Dimensions: 70 mm deep, 39.1 mm wide, 90 mm high – fits standard 100 mm enclosure depth. Sits on DIN rail; power delivered through a removable screw terminal block. Sensor wiring uses eight RJ11 connectors. Dielectric strength: 500 V between I/O and external supply, 2500 V between I/O and internal logic. Photocoupler insulation per channel.

Frequently asked questions

What is the depth of the TM2ARI8LRJ module?

The depth is 2.8 in (70 mm).

What is the width of the TM2ARI8LRJ module?

The width is 1.5 in (39.1 mm).

MPN