Skip to main content
Schneider Electric TM3TI4DG

Schneider TM3TI4DG Analog Input Module, 4-channel Thermocoup

MPNTM3TI4DG
Active

Schneider Electric Modicon TM3, analog input module, TM3TI4DG, 4 thermocouple inputs, 16-bit resolution, LSB 0.1°C.

$306.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

TM3TI4DG key specifications
ParameterValue
Type of cableTwisted shielded pairs cable <30 m for input circuit
Range of productModicon TM3
Analogue input typeThermocouple - 200...1000 °C thermocouple J Thermocouple - 200...1300 °C thermocouple K Thermocouple 0...1760 °C thermocouple R Thermocouple 0...1760 °C thermocouple S Thermocouple 0...1820 °C thermocouple B Thermocouple - 200...400 °C thermocouple T Thermocouple - 200...1300 °C thermocouple N Thermocouple - 200...800 °C thermocouple E Thermocouple 0...2315 °C thermocouple C
Product or component typeAnalog input module
Typical current consumption45 mA at 5 V DC 50 mA at 5 V DC 35 mA at 24 V DC 40 mA at 24 V DC
IP degree of protectionIP20
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
Electrical connection10 x 1.5 mm² removable spring terminal block with pitch 3.81 mm adjustment for inputs and supply 10 x 1.5 mm² removable spring terminal block with pitch 3.81 mm adjustment for inputs
Pollution degree2
Shock resistance15 gn for 11 ms
Relative humidity10...95 % without condensation
Operating altitude0...2000 m

All specifications

TM3TI4DG additional specifications
ParameterValue
Vibration resistance3.5 mm (f = 5...8.4 Hz) on DIN rail 3 gn (f = 8.4...150 Hz) on DIN rail
Depth70 mm
Width23.6 mm
Height90 mm
StandardsIEC 61131-2
MarkingCE
LSB value0.1 °C
Cross talk<= 1 LSB
InsulationBetween output and supply at 1500 V AC Between output and internal logic at 500 V AC
Non-linearity+/- 0.2 %FS
Conversion time100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple
Input impedance>= 1 MOhm
Repeat accuracy+/-0.5 %FS
Local signalling1 LED green for PWR
Sampling duration100 ms
Temperature drift+/- 0.01 %FS/°C
Analogue input number4
Absolute accuracy error+/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C +/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C +/- 0.2 % of full scale at 25 °C for thermocouple B 300...1820 °C +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple K 0...1300 °C +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple J 0...1000 °C +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple E 0...800 °C +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple T 0...400 °C +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple N 0...1300 °C
Immunity to microbreaks10 ms
Electromagnetic emissionRadiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30...230 MHz conforming to IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230...1000 MHz conforming to IEC 55011
Analogue input resolution16 bits 15 bits + sign
Permissible continuous overload13 V, analogue input type: voltage 40 mA, analogue input type: current
Ambient air temperature for storage-25...70 °C
Ambient air temperature for operation-10...55 °C (horizontal installation) -10...35 °C (vertical installation)

Product details

Thermocouple coverage and accuracy

The TM3TI4DG is a 4-channel thermocouple input module for the Modicon TM3 platform, with 16-bit resolution and a 0.1°C LSB. It supports nine thermocouple types: J (–200 to 1000°C), K (–200 to 1300°C), R (0 to 1760°C), S (0 to 1760°C), B (300 to 1820°C), T (–200 to 400°C), N (–200 to 1300°C), E (–200 to 800°C), and C (0 to 2315°C). Conversion time for a single channel is 100 ms, plus 100 ms per active channel, plus one controller cycle—sufficient for ramp/soak profiles in glass melting or heat treating.

Mounting and environmental considerations

Mounts on TH35-15 or TH35-7.5 DIN rail per IEC 60715, or on a plate with the fixing kit. Width is 23.6 mm. The removable spring terminal block accepts 1.5 mm² wire, pitch 3.81 mm. Input circuits require twisted shielded pair cable under 30 m. Input impedance is ≥1 MΩ. Conversion time includes the controller cycle, so factor that into the task scan. Rated for horizontal operation from –10 to 55°C, or vertical (derated to 35°C). IP20, pollution degree 2, operates at altitudes up to 2000 m. Vibration resistance on DIN rail: 3.5 mm at 5–8.4 Hz, 3 gn at 8.4–150 Hz. Shock: 15 gn for 11 ms. Power draw is 45 mA at 5 V DC and 35 mA at 24 V DC from the backplane. A green PWR LED indicates module supply is present.

Frequently asked questions

What compliance documentation does this module carry?

The module is CE marked and designed to IEC 61131-2 standards.

What are the key ratings of the TM3TI4DG?

It provides 4 thermocouple inputs with 16-bit resolution, 0.1°C LSB, support for nine thermocouple types (J, K, R, S, B, T, N, E, C), and typical accuracy of ±0.2% FS at 25°C.

What is the width of the TM3TI4DG?

The width is 23.6 mm, fitting on standard DIN rail.

What is the depth of the TM3TI4DG?

The depth is 70 mm.

MPN