Skip to main content
Schneider Electric TM5SAO2H

Schneider TM5SAO2H Modicon TM5 Analog Output Module, 2 Ch, 1

MPNTM5SAO2H
Active

Schneider Modicon TM5 Analog Output Module, 2 channels, current/voltage, 12.5 mm width, CE, UL 508, CSA, IEC 61131-2.

$638.00 – $656.48Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

TM5SAO2H key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon TM5
Analogue output typeCurrent: 0...20 mA Voltage: +/- 10 V
Product or component typeAnalog output module
Supply voltage24 V DC -15...20 %
Typical current consumption2 mA at 5 V DC
Power dissipation in1.21 W
IP degree of protectionIP20
Response time<= 1 ms
Response time on output<= 1 ms
Pollution degree2
Shock resistance15 gn for 11 ms

All specifications

TM5SAO2H additional specifications
ParameterValue
Relative humidity5...95 % without condensation
Operating altitude0...2000 m
Vibration resistance1 gn (f = 8.4...150 Hz) on DIN rail 3.5 mm (f = 5...8.4 Hz) on DIN rail
Depth75 mm
Width12.5 mm
ColorWhite
Height99 mm
Housing colourWhite
StandardsCSA C22.2 No 213 UL 508 CSA C22.2 No 142 IEC 61131-2
SupplyInternal
MarkingCE
Non-linearity< 0.007 %FS/°C, analogue output type: current < 0.007 %FS/°C, analogue output type: voltage
Local signalling1 LED green for power supply 1 LED red for power supply 2 LEDs yellow for output status
Measurement error< 0.045 % of full scale +/- 10 V 25 °C < 0.045 % of full scale 0...20 mA 25 °C
Sampling duration50 ms
Analogue output number2
Measurement resolution305.176 µV, +/- 10 V 610.352 nA, 0...20 mA
Temperature coefficient0.015 %FS/°C, analogue output type: current 0.015 %FS/°C, analogue output type: voltage
Isolation between channels and bus500 Vrms AC
Ambient air temperature for storage-25...70 °C
Ambient air temperature for operation0...55 °C without derating (horizontal installation) 0...60 °C with derating factor (horizontal installation) 0...50 °C (vertical installation)

Product details

2-Channel Analog Output for the Modicon TM5 Platform

The Schneider TM5SAO2H is a 2-channel analog output module within the Modicon TM5 system, providing current (0...20 mA) and voltage (±10 V) outputs with a response time ≤1 ms and a width of 12.5 mm. Each output is individually configurable, supporting current loops or bipolar voltage signals. Measurement resolution is 610.352 nA on the current range and 305.176 µV on the voltage range, with a 50 ms sampling duration. The module is powered internally from the backplane (24 V DC -15...20 %), drawing 2 mA at 5 V DC, and dissipates 1.21 W. Local signaling includes three LEDs: green for power, red for power fault, and two yellow for output status.

Comparison: TM5SAO2H vs. TM5SAO4H

The TM5SAO4H is a 4-channel variant sharing the same 12.5 mm × 75 mm × 99 mm mechanical footprint, making the TM5SAO2H a mechanical drop-in replacement when channel count is the only difference. Key functional differences: the TM5SAO4H offers a faster sampling duration of 50 µs (vs. 50 ms on the TM5SAO2H) and better non-linearity of <0.005 %FS (vs. <0.007 %FS). The TM5SAO2H has a slightly lower power dissipation (1.21 W vs. 1.51 W). For a BOM needing exactly two outputs and moderate speed, the TM5SAO2H is the correct choice. If future expansion to four outputs or faster loop updates is expected, the TM5SAO4H avoids a later swap.

Integration Notes

Mounts on a DIN rail within the Modicon TM5 backplane. Pollution degree 2, IP20. Operating ambient 0...55 °C horizontal, up to 60 °C with derating, 0...50 °C vertical. Shock 15 gn for 11 ms; vibration 1 gn (8.4...150 Hz) on rail, 3.5 mm (5...8.4 Hz). Use shielded cable for analog signals to maintain accuracy. Isolation between channels and bus is 500 Vrms AC. The module carries CE marking and complies with UL 508, CSA C22.2 No 142 and 213, and IEC 61131-2. Temperature coefficient is 0.015 %FS/°C for both current and voltage outputs.

Frequently asked questions

Will the TM5SAO2H drop into a panel designed for the TM5SAO4H?

Yes, they share identical dimensions (12.5 mm width, 75 mm depth, 99 mm height) and mounting, so the TM5SAO2H fits mechanically. The wiring will differ since the TM5SAO4H has four outputs.

What compliance standards does the TM5SAO2H meet?

CE marked, UL 508 listed, CSA C22.2 No 142 and No 213, and IEC 61131-2 compliant.

What is the sampling duration and response time?

The sampling duration is 50 ms; the output response time is ≤1 ms.

MPN