Skip to main content
Schneider Electric TM5SDI4D

Schneider Electric TM5SDI4D

MPNTM5SDI4D
Active

DISCRETE INPUT MODULE, MODICON T

$48.37 – $103.59Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

TM5SDI4D key specifications
ParameterValue
Range of productModicon TM5
Product or component typeDiscrete input module
Maximum voltage drop<2 V at 500 mA sensor supply
Discrete input voltage24 V DC 20.4...28.8 V)
Voltage state 0 guaranteed<= 5 V
Voltage state 1 guaranteed>= 15 V
Discrete input current3.75 mA at 24 V DC
Typical current consumption28 mA 5 V DC 25 mA 24 V DC
Power dissipation in0.73 W
IP degree of protectionIP20
Electrical connection3 wires
Pollution degree2

All specifications

TM5SDI4D additional specifications
ParameterValue
Shock resistance15 gn 11 ms
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m)
Vibration resistance1 gn 8.4...150 Hz) on DIN rail 3.5 mm 5...8.4 Hz) on DIN rail
Depth3.0 in (75 mm)
Width0.5 in (12.5 mm)
Height3.9 in (99 mm)
StandardsIEC 61131-2 CSA C22.2 No 142 UL 508 CSA C22.2 No 213
MarkingCE
CategoryUS1PC1222532
Input filtering<= 100 ms hardware
Input impedance6.4 kOhm
Local signalling1 LED (green) for power supply 1 LED (red) for power supply 4 LEDs (green) for input status
Discrete input logicSink
Discrete input number4 at 24 V DC
Electromagnetic compatibilityElectrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2 Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2 Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz IEC 61000-4-3 Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3 Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4 Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4 Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4 1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5 1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5 Conducted RF disturbances IEC 61000-4-6 Conducted and radiated emissions CISPR 11
Ambient air temperature for storage-40...158 °F (-40...70 °C)
Ambient air temperature for operation14...131 °F (-10...55 °C) without derating horizontal installation) 14...140 °F (-10...60 °C) with derating factor horizontal installation) 14...122 °F (-10...50 °C) vertical installation)
MPN