Schneider Electric TM5SDO2TFS

TM5SDO2TFS Modicon TM5 Safety Output Module, Obsolete

MPNTM5SDO2TFS
Obsolete

Modicon TM5 safety DC discrete output module, TM5SDO2TFS, 2 solid-state outputs, 24 V DC, 0.5 A per channel, SIL 3 / PL e.

$391.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

TM5SDO2TFS key specifications
ParameterValue
Range of productModicon TM5
Product or component typeSafety dc discrete output module
Discrete output voltage24 V DC 20.4...28.8 V)solid state
Current per channel0.5 A
Peak output current12 A
Maximum leakage current10 µA 24 V DC when switched off
Maximum current per output common1 A
Switching frequency<= 500 Hz resistive
IP degree of protectionIP20
Electrical connection2 wires
Pollution degree2
Shock resistance15 gn 11 ms

All specifications

TM5SDO2TFS additional specifications
ParameterValue
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m)
Vibration resistance1 gn 8.4...150 Hz) on DIN rail 3.5 mm 5...8.4 Hz) on DIN rail
Depth3.0 in (75 mm)
Width1.0 in (25 mm)
Height3.9 in (99 mm)
StandardsCSA C22.2 No 142 EN 13849-1 IEC 61508 IEC 62061 UL 508 IEC 61131-2
MarkingCE
CategoryUS1PC5218360
Safety levelSIL 3 IEC 61508 SIL 3 IEC 62061 PL = e EN 13849-1
Local signalling1 LED (green) for power supply 1 LED (red) for power supply 2 LEDs (red) for safety status 2 LEDs (red/orange) for output status
Discrete output logicSource
Discrete output number2 solid state at 24 V DC
Safety reliability dataMTTFd > 100 years PFD < 1E-5 PFH < 1E-9
Electromagnetic compatibilityElectrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2 Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2 Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3 Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4 Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4 Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4 1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5 1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5 Conducted RF disturbances IEC 61000-4-6 Conducted and radiated emissions CISPR 11
Ambient air temperature for storage-40...158 °F (-40...70 °C)
Ambient air temperature for operation14...122 °F (-10...50 °C) vertical installation) 14...131 °F (-10...55 °C) horizontal installation)

Product details

The TM5SDO2TFS is a safety-rated DC discrete output module from the Modicon TM5 family – two solid-state source outputs, each rated 0.5 A continuous with a peak capability of 12 A. It switches loads on the 24 V DC control voltage rail, and the outputs are watchdog-monitored for safety logic. It carries SIL 3 per IEC 61508 and IEC 62061, and PL e per EN 13849-1. The safety reliability data shows MTTFd > 100 years, PFD < 1E-5, PFH < 1E-9 – numbers that slot easily into a risk-assessment report without extra derating. The module occupies a single 25 mm wide slot in the TM5 backplane and draws power from the bus. It is IP20-protected, rated for pollution degree 2, and has a switching frequency up to 500 Hz for resistive loads. Off-state leakage is 10 µA at 24 V – negligible for most safety circuits.

This module mounts directly into a TM5 bus base and communicates over the backplane with the safety PLC or safety CPU. There are no fieldbus settings to configure. Installation rules: vertical mounting allows an ambient temperature range of -10 to 50 °C; horizontal (sideways) extends to 55 °C. Vibration resistance is 1 gn on DIN rail across 8.4–150 Hz. The module meets IEC 61131-2 and carries CE marking, UL 508, and CSA C22.2 No 142.

Frequently asked questions

What are the key electrical ratings of TM5SDO2TFS?

It has two solid-state source outputs rated 0.5 A per channel (continuous), 12 A peak, switching up to 500 Hz on resistive loads. Output voltage range is 20.4–28.8 V DC. Leakage current is 10 µA off-state.

What safety certifications does TM5SDO2TFS carry?

It is certified SIL 3 per IEC 61508 and IEC 62061, and PL e per EN 13849-1. It also meets UL 508, CSA C22.2 No 142, and carries CE marking. The safety reliability data is MTTFd >100 years, PFD <1E-5, PFH <1E-9.

MPN