Skip to main content
Schneider Electric VW3A46105A — AC Drive (VFD) 480V

Schneider Electric VW3A46105A Passive Filter, 33 A, 380-480

MPNVW3A46105A
Active

Schneider Electric VW3A46105A passive filter, ATV610 series, 33 A output, 380-480 V, 15 kW/20 hp, 50 Hz.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A46105A — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A46105A — Input / Supply
ParameterValue
Rated supply voltage range380...480 V +/- 10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A46105A — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 (enclosure mounting)

Environmental

VW3A46105A — Environmental
ParameterValue
Operating ambient temperature-25...45 °C (without current derating)
Storage / transport temperature-25...85 °C storage in original packaging

Approvals

VW3A46105A — Approvals
ParameterValue
Standards complianceUL 61800-5-1 IEC 61800-5-1

Other specifications

VW3A46105A — Other specifications
ParameterValue
THDI10 % for variable speed drive ATV610
Efficiency98 %
Thermal losses327 W
Quantity per drive1 filter per drive for variable speed drive ATV610 motor: 15 kW/20 hp
Current22.2 A for input 33 A for output
Electrical connectionL1, L2, L3, L1', L2', L3' terminal, connection capacity: 0.5...10 mm² D1, D2, D3, D1', D2', D3' terminal, connection capacity: 2.5 mm² TS, TS' terminal, connection capacity: 0.5...4 mm²
Power supply frequency50 Hz +/- 2 %
Electrical insulation classClass N

Product details

The VW3A46105A is a passive input filter sized for one ATV610 variable speed drive at 15 kW / 20 hp. It clamps line-side current THDI to 10 %, which keeps harmonic distortion within IEEE 519 guidelines for most commercial installations without needing a separate active front end. Rated for 380-480 V ±10 % three-phase, 50 Hz ±2 %. Input current rating is 22.2 A; output side carries 33 A. Efficiency runs at 98 %, with 327 W thermal losses that need to be vented from the enclosure — IP20 construction means it is intended for inside a panel, not open-floor mounting. Terminals accept 0.5-10 mm² for the line/load power connections and 2.5 mm² for the DC-link choke connections (D1-D3). The TS/TS' thermistor terminals take 0.5-4 mm².

Compliance documentation covers UL 61800-5-1 and IEC 61800-5-1 for adjustable-speed drive systems. The filter is Class N insulation rated.

Mounts inside a panel — IP20 requires the enclosure to provide the environmental seal. One filter per drive, wired between the line supply and the ATV610 input. The 50 Hz ±2 % line frequency constraint means it is not suitable for 60 Hz mains without checking the drive's DC-bus ripple limits.

Frequently asked questions

What THDI does the VW3A46105A achieve?

The filter limits input current THDI to 10 % when used with an ATV610 drive at the rated 15 kW / 20 hp load point.

What standards does VW3A46105A comply with?

It is certified to UL 61800-5-1 and IEC 61800-5-1, the adjustable-speed drive system safety standards.

Where can I buy VW3A46105A and how is it quoted?

The VW3A46105A is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN