Skip to main content
Schneider Electric VW3A46106A — AC Drive (VFD) 480V

Schneider VW3A46106A Passive Filter, 42 A, 380-480 V, for AT

MPNVW3A46106A
Active

Schneider Electric VW3A46106A passive filter, for ATV610 drive, 42 A output, 380-480 V, 19 kW/25 hp, 50 Hz, THDI 10 %, efficiency 98 %.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A46106A — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A46106A — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 10...10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A46106A — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 (enclosure mounting)

Environmental

VW3A46106A — Environmental
ParameterValue
Operating ambient temperature-25...45 °C (without current derating)
Storage / transport temperature-25...85 °C storage in original packaging

Approvals

VW3A46106A — Approvals
ParameterValue
Standards complianceUL 61800-5-1 IEC 61800-5-1

Other specifications

VW3A46106A — Other specifications
ParameterValue
THDI10 % for variable speed drive ATV610
Efficiency98 %
Thermal losses244 W
Quantity per drive1 filter per drive for variable speed drive ATV610 motor: 19 kW/25 hp
Current27.3 A for input 42 A for output
Electrical connectionL1, L2, L3, L1', L2', L3' terminal, connection capacity: 0.5...10 mm² D1, D2, D3, D1', D2', D3' terminal, connection capacity: 2.5 mm² TS, TS' terminal, connection capacity: 0.5...4 mm²
Power supply frequency50 Hz +/- 2 %
Electrical insulation classClass N

Product details

The Schneider Electric VW3A46106A is a passive filter designed for the ATV610 variable speed drive family. It cleans up the line-side harmonics, pulling the current THD down to 10 % — that's the spec that keeps you out of trouble with utility power-quality requirements and stops nuisance tripping of upstream breakers. Rated for a 19 kW / 25 hp motor on a 380-480 V three-phase supply, it handles 27.3 A on the input side and 42 A on the output. One filter per drive — no sharing.

Efficiency and thermal reality

Efficiency is 98 %, with 244 W of thermal losses. Ambient air temperature for operation is -25 to 45 °C without current derating.

Carries UL 61800-5-1 and IEC 61800-5-1 — the adjustable-speed drive safety standards. That covers the electrical safety and thermal protection for the drive system. IP20 rated, so it's for enclosure mounting only, not washdown areas. This is a current catalog item.

Wiring and integration

Terminals accept 0.5 to 10 mm² for line and load phases, 2.5 mm² for DC choke connections, and 0.5 to 4 mm² for the temperature switch. Supply frequency is 50 Hz.

Frequently asked questions

What is the THDI of VW3A46106A?

The filter achieves 10 % current total harmonic distortion (THDI) when used with the ATV610 drive at its rated load.

What standards does VW3A46106A comply with?

It meets UL 61800-5-1 and IEC 61800-5-1, the safety standards for adjustable-speed drive systems.

MPN