Skip to main content
Schneider Electric VW3A46110A — AC Drive (VFD) 480V

Schneider VW3A46110A Passive Filter, 99A, 380-480V, 45kW, TH

MPNVW3A46110A
Active

Schneider Electric Altivar Easy series, passive harmonic filter, VW3A46110A, 99 A output, 380-480 V, 45 kW, 50 Hz, THDI 10%.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A46110A — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A46110A — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 10...10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A46110A — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 (enclosure mounting)

Environmental

VW3A46110A — Environmental
ParameterValue
Operating ambient temperature-25...45 °C (without current derating)
Storage / transport temperature-25...85 °C storage in original packaging

Approvals

VW3A46110A — Approvals
ParameterValue
Standards complianceUL 61800-5-1 IEC 61800-5-1

Other specifications

VW3A46110A — Other specifications
ParameterValue
THDI10 % for variable speed drive ATV610
Efficiency98 %
Thermal losses448 W
Quantity per drive1 filter per drive for variable speed drive ATV610 motor: 45 kW/60 hp
Current99 A for output 66.6 A for input
Electrical connectionL1, L2, L3, L1', L2', L3' terminal, connection capacity: 16...50 mm² D1, D2, D3, D1', D2', D3' terminal, connection capacity: 8 mm² TS, TS' terminal, connection capacity: 0.5...4 mm²
Power supply frequency50 Hz +/- 2 %
Electrical insulation classClass N

Product details

What this filter does for your drive line

The VW3A46110A is a passive harmonic filter sized for one Schneider ATV610 variable speed drive running a 45 kW (60 hp) motor. It knocks input current THDI down to 10%—that's the figure that keeps your plant from failing IEEE 519 or G5/4 harmonics surveys. You bolt one filter per drive; no sharing across multiple units. Rated for 380-480 V three-phase, 50 Hz supply. Output current is 99 A; input side sees 66.6 A. Efficiency runs 98%, so the 448 W of thermal loss goes into the cabinet air—plan your ventilation accordingly.

IP20 rated, so it lives inside an enclosure—not out in the weather or a washdown zone. The power terminals accept 16 to 50 mm² cable on /L2/L3 and '/L2'/L3'. The D1/D2/D3 and D1'/D2'/D3' terminals take 8 mm². The TS/TS' terminals for the thermal switch are 0.5 to 4 mm². Strip and torque per the Schneider instruction sheet. Store it in original packaging from -25 to 85 °C. If your panel runs hotter than 45 °C, you'll need to derate or move the filter to cooler air.

Frequently asked questions

What is the THDI rating of VW3A46110A?

It achieves 10% THDI when used with an ATV610 variable speed drive. That's the input current harmonic distortion after the filter—clean enough to pass most utility and plant harmonic limits.

What standards does VW3A46110A comply with?

It complies with UL 61800-5-1 and IEC 61800-5-1, the safety standards for adjustable-speed drive systems. Electrical insulation class N.

Where can I buy VW3A46110A and how is it quoted?

This filter is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN