Skip to main content
Schneider Electric VW3A46111 — AC Drive (VFD) 480V

Schneider VW3A46111 Passive Filter, 105A, 400V, 50Hz, for Al

MPNVW3A46111
Active

Schneider Electric, Altivar passive filter, VW3A46111, 105 A rated current, 400 V, 50 Hz, for variable speed drives up to 55 kW/75 hp.

$8,465.62Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

VW3A46111 — Identification
ParameterValue
Product typePassive filter
VW3A46111 — Input / Supply
ParameterValue
Rated supply voltage range400 V +/- 10 %
Network number of phases3 phases
VW3A46111 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 IP55 (enclosure mounting)
VW3A46111 — Environmental
ParameterValue
Operating ambient temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C storage in original packaging -25...65 °C during transport
Vibration resistance2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6
VW3A46111 — Approvals
ParameterValue
Standards complianceIEC 61000-3-4 IEC 61000-3-2 IEC 61000-3-12 IEC 61000-2-2 G5/4 engineering recommendation IEC 61000-2-4

Product details

The Schneider VW3A46111 is a passive filter designed to reduce current harmonics on Altivar variable speed drives up to 55 kW/75 hp. It sits between the line supply and the drive input, cleaning up the current waveform so the installation meets IEC 61000-3-4, IEC 61000-3-12, and G5/4 harmonic limits. One filter per drive — no sharing across multiple units. Rated 101 A input and 105 A output at 400 V ±10 %, 50 Hz three-phase. That 105 A output rating is the figure to size conductors and upstream protection by — the input side is slightly lower because the filter itself draws magnetising current.

THDI is 10 % on ATV61W, ATV650, ATV630, ATV950, and ATV930; 16 % on ATV61H and ATV71H/W. Residual harmonic current after filtering. Power factor correction is load-dependent: 0.99 at full load, 0.85 at 75 % load, and unity (1.0) at 150 % overload for up to 60 seconds. The filter's 98 % efficiency means 488 W of heat to dump into the enclosure — plan the cabinet ventilation around that, especially if the drive and filter share the same IP20 panel.

This filter is still the current production part for the Altivar range it supports.

Frequently asked questions

What drives does the VW3A46111 filter work with?

It fits Altivar ATV61W, ATV61H, ATV71H, ATV71W, ATV650, ATV630, ATV950, and ATV930 drives rated 55 kW/75 hp. One filter per drive — not shared across multiple units.

What THDI does the VW3A46111 achieve?

THDI is 10 % on ATV61W, ATV650, ATV630, ATV950, and ATV930 drives; 16 % on ATV61H and ATV71H/W drives. That's the residual harmonic current after filtering.

What compliance standards does the VW3A46111 meet?

It complies with IEC 61000-3-4, IEC 61000-3-2, IEC 61000-3-12, IEC 61000-2-2, IEC 61000-2-4, and the UK G5/4 engineering recommendation for harmonic emissions.

MPN
VW3A46111