Skip to main content
Schneider Electric VW3A46113 — AC Drive (VFD) 480V

Schneider VW3A46113 Passive Filter, 187A, 400V, 50Hz

MPNVW3A46113
Active

Schneider Electric Altivar series passive harmonic filter, VW3A46113, 187 A output, 400 V, 50 Hz, THDI 10 %.

$12,983.14Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

VW3A46113 — Identification
ParameterValue
Product typePassive filter
VW3A46113 — Input / Supply
ParameterValue
Rated supply voltage range400 V +/- 10 %
Network number of phases3 phases
VW3A46113 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 IP55 (enclosure mounting)
VW3A46113 — Environmental
ParameterValue
Operating ambient temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C storage in original packaging -25...65 °C during transport
Vibration resistance2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6
VW3A46113 — Approvals
ParameterValue
Standards complianceG5/4 engineering recommendation IEC 61000-3-12 IEC 61000-3-4 IEC 61000-2-2 IEC 61000-3-2 IEC 61000-2-4

Product details

The Schneider VW3A46113 is a passive harmonic filter sized for Altivar drives in the 90–110 kW range. It knocks line-current THDI down to 10 % at full load, which keeps the installation inside IEC 61000-3-12 and G5/4 limits — the kind of compliance a grid operator or site spec will flag before energising a multi-drive line. Rated 180 A input, 187 A output on a 400 V three-phase supply at 50 Hz. The 1.5× nominal overload for 60 s handles the inrush a motor pulls during acceleration without the filter saturating.

THDI 10 % at rated load is the headline number — it tells the site engineer the filter will clean up the drive's current harmonics to a level that passes most utility-imposed distortion limits. The 98 % efficiency means 743 W of thermal loss to vent; that heat lands inside the enclosure, so the panel cooling budget needs to account for it. Cos phi varies with load: unity at 150 % line current, 0.99 at full load, dropping to 0.85 at 75 % load. That curve is normal for a passive filter — the power-factor correction is strongest when the drive is working hardest. Operating temperature runs 5–45 °C without derating; above that, derate 3 % per °C up to 60 °C. Altitude derating kicks in above 1000 m at 5 % per 1000 m. If the filter is going into a plant in Bogotá or a hot mezzanine, those curves decide whether the 187 A rating holds.

Deployment and mounting

IP20 base, IP55 when mounted in an enclosure — so it lives inside a panel, not out in the weather. The terminals split into two groups: A/B for the control wiring (2.5 mm²) and X1-1 through X2-3 for the power conductors (2.5–90 mm²). That range covers the cable sizes for a 90–110 kW drive feed. One filter per drive, matched to the specific Altivar model and power rating. The compatibility list covers ATV61H, ATV71H, ATV61Q, ATV71Q at 110 kW/150 hp, and ATV630, ATV650, ATV930, ATV950 at 90 kW/125 hp.

Frequently asked questions

Where can I buy VW3A46113 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is VW3A46113's listed THDI?

THDI is 10 % at rated load for the listed Altivar drives: ATV61H and ATV71H at 110 kW/150 hp, and ATV630, ATV650, ATV930, ATV950 at 90 kW/125 hp.

What compliance documentation does this filter carry?

The filter complies with IEC 61000-3-12, IEC 61000-3-4, IEC 61000-2-2, IEC 61000-3-2, IEC 61000-2-4, and the G5/4 engineering recommendation.

MPN
VW3A46113