Schneider Electric VW3A46116 — AC Drive (VFD) 480V

VW3A46116 Passive Filter, 316 A, 400 V, THDI 10%, Altivar

MPNVW3A46116
Active

Schneider Electric Altivar passive filter, VW3A46116, 316 A output, 400 V, 50 Hz, THDI 10 %, 98 % efficiency.

$17,539.12Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

VW3A46116 — Identification
ParameterValue
Product typePassive filter
VW3A46116 — Input / Supply
ParameterValue
Rated supply voltage range400 V +/- 10 %
Network number of phases3 phases
VW3A46116 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 IP55 (enclosure mounting)
VW3A46116 — Environmental
ParameterValue
Operating ambient temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C storage in original packaging -25...65 °C during transport
Vibration resistance2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6
VW3A46116 — Approvals
ParameterValue
Standards complianceIEC 61000-2-2 IEC 61000-2-4 IEC 61000-3-12 IEC 61000-3-4 G5/4 engineering recommendation IEC 61000-3-2

Product details

What this filter does on the line side

The VW3A46116 is a passive filter that reduces current harmonics from Altivar variable speed drives. It sits between the line supply and the drive, reducing THDI to 10 % for drive sizes from 160 kW to 355 kW. Rated at 304 A input and 316 A output on a 400 V +/- 10 % three-phase network at 50 Hz, it handles the full-load current of the drives it pairs with. The 98 % efficiency figure means only 2 % of the power passing through is lost as heat — which at 925 W thermal losses is still enough to require ventilation clearance in the cabinet.

Sizing and quantity per drive

The filter can handle 1.5 times nominal current for 60 seconds, which covers short-duration overloads during motor acceleration. Ambient temperature derating kicks in above 45 °C: 3 % current reduction per °C up to 60 °C. Below 45 °C, no derating needed.

Installation and wiring

Wiring uses two terminal blocks: an A/B terminal for 2.5 mm² control connections, and an X1-1 through X2-3 terminal for 25 to 300 mm² power cable.

Beyond the harmonic standards (IEC 61000-2-2, IEC 61000-2-4, IEC 61000-3-12, IEC 61000-3-4, G5/4), the filter carries Class F insulation and operates across 5 to 45 °C without derating, with storage from -25 to 55 °C in original packaging. Relative humidity tolerance is 5 to 85 % without condensation. Altitude derating applies above 1000 m — 5 % per additional 1000 m up to 4000 m.

Frequently asked questions

What drives does VW3A46116 work with?

It works with Altivar ATV61, ATV71, ATV630, and ATV930 drives from 160 kW up to 355 kW. The quantity per drive varies — one filter for 160 kW wall-mount drives, two for 315 kW and 355 kW units.

What is the THDI rating of VW3A46116?

The filter achieves a total harmonic current distortion (THDI) of 10 % across all supported drive sizes and series.

What is the power factor (cos phi) of this filter?

The cos phi varies with load: 1 at 150 % of line current, 0.99 at 100 % of line current, and 0.85 at 75 % of line current.

What compliance documentation does VW3A46116 carry?

The filter complies with IEC 61000-2-2, IEC 61000-2-4, IEC 61000-3-12, IEC 61000-3-4, and G5/4 engineering recommendation for harmonic limits. It carries Class F insulation and is tested for vibration resistance per IEC 60068-2-6.