Skip to main content
Schneider Electric VW3A4612 — AC Drive (VFD) 480V

VW3A4612 Altivar passive filter, 289 A, 400 V, obsolete

MPNVW3A4612
Obsolete

Schneider Altivar passive filter, 289 A, 400 V, 50 Hz, for variable speed drive harmonic reduction.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

VW3A4612 — Identification
ParameterValue
Product typePassive filter
VW3A4612 — Input / Supply
ParameterValue
Rated supply voltage range400 V +/- 10 %
Network number of phases3 phases
VW3A4612 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20
VW3A4612 — Environmental
ParameterValue
Operating ambient temperature40...55 °C (with current derating 3 % per °C) 5...40 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C

Product details

The Schneider VW3A4612 is a passive filter designed to reduce current harmonics on Altivar variable-speed drives. Rated at 289 A and 400 V ±10 %, 50 Hz, it delivers a THDI of 10 % on the ATV61 and ATV71 drives listed — meaning it cleans up the line-side current distortion to that level under rated load.

Mounts as an external line filter — IP20 enclosure, bare-wire connection (16.5 mm diameter). Quantity per drive varies by model: one filter for a 160 kW drive (ATV61HC16N4 or ATV71HC16N4), two for 280–355 kW frames, three for 500 kW frames. Plan the panel space accordingly.

Performance details

Efficiency is 98 %. Cos phi varies with load: 1 at 150 % line current, 0.99 at 100 %, 0.85 at 75 % — so the filter maintains near-unity power factor across a wide load band. Max current is 1.5× nominal; Class F insulation. Operating temperature range is 5–40 °C without derating, 40–55 °C with 3 % per °C derating. Altitude derating applies above 1000 m (5 % per 1000 m).

Frequently asked questions

Where can I buy VW3A4612?

We source the VW3A4612 through independent distribution and surplus channels. Submit an RFQ; availability and pricing are confirmed at quote time.

What THDI does the VW3A4612 achieve?

It achieves a THDI of 10 % on the listed ATV61 and ATV71 drives (e.g., ATV61HC16N4, ATV71HC16N4, and others up to 500 kW).

What is the cos phi of the VW3A4612?

Cos phi is 1 at 150 % line current, 0.99 at 100 % line current, and 0.85 at 75 % line current.

How many VW3A4612 filters are needed per drive?

One filter for 160 kW drives, two for 280–355 kW drives, and three for 500 kW drives.

MPN