Schneider Electric VW3A46165 — AC Drive (VFD) 480V

VW3A46165 Passive Filter, 50 A, 480 V, 60 Hz, for Altivar Dr

MPNVW3A46165
Active

Schneider Electric Altivar series, VW3A46165 passive filter, 48 A input / 50 A output, 480 V +/- 10 %, 60 Hz, for variable speed drives.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A46165 — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A46165 — Input / Supply
ParameterValue
Rated supply voltage range480 V +/- 10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A46165 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 IP55 (enclosure mounting)

Environmental

VW3A46165 — Environmental
ParameterValue
Operating ambient temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C storage in original packaging -25...65 °C during transport
Vibration resistance2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6

Approvals

VW3A46165 — Approvals
ParameterValue
Standards complianceIEC 61000-3-12 IEC 61000-2-2 G5/4 engineering recommendation IEC 61000-2-4 IEC 61000-3-2 IEC 61000-3-4

Product details

The VW3A46165 is a passive harmonic filter for line-side installation on variable-speed drives, reducing current harmonics. It is rated for 48 A input and 50 A output at 480 V +/- 10 %, 60 Hz +/- 2 %, and is intended for one filter per drive on Altivar ATV630, ATV650, ATV930, and ATV950 units sized for 30 kW / 40 hp motors. The THDI performance varies by drive model: 10 % for ATV61H, ATV71H, and ATV71W, and 5 % for ATV61W, ATV630, ATV650, ATV930, and ATV950. That means on a 30 kW ATV630, the filter knocks harmonic distortion down to 5 % of fundamental — clean enough to meet IEC 61000-3-12 and G5/4 engineering recommendation limits without an active front end. Efficiency is 98 %, with 482 W of thermal losses to manage inside the enclosure. The filter is IP20 as standard, IP55 when enclosure-mounted, so plan for ventilation or derating if the panel runs hot.

Sizing and derating notes

Operating temperature range is 5 to 45 °C without derating; from 45 to 60 °C, derate current by 3 % per °C. Above 1000 m altitude, derate 5 % per additional 1000 m. The filter draws 48 A on the input side and passes 50 A to the drive — the 2 A difference covers filter losses and magnetising current. Terminals accept 1.5 to 25 mm² on the main power connections and 2.5 mm² on the control terminals. Vibration resistance is 2 mm peak-to-peak at 5-13.2 Hz and 0.7 gn at 13.2-150 Hz per IEC 60068-2-6. Class F insulation (155 °C) gives headroom for the 482 W of self-heating. The power factor correction effect varies with load: cos phi is 1 at 150 % of line current, 0.99 at 100 %, and 0.85 at 75 % — meaning the filter presents a near-unity power factor to the line under normal load.

Frequently asked questions

What THDI does the VW3A46165 achieve?

THDI is 10 % for ATV61H, ATV71H, and ATV71W drives, and 5 % for ATV61W, ATV630, ATV650, ATV930, and ATV950 drives — all at 30 kW / 40 hp motor rating. The filter meets IEC 61000-3-12 and G5/4 limits at those levels.

What is the rated current and voltage for VW3A46165?

Input rated current is 48 A, output rated current is 50 A. Supply voltage is 480 V +/- 10 %, 60 Hz +/- 2 %. The filter is a three-phase passive type.

What compliance standards does VW3A46165 meet?

The filter complies with IEC 61000-3-12, IEC 61000-2-2, G5/4 engineering recommendation, IEC 61000-2-4, IEC 61000-3-2, and IEC 61000-3-4. Vibration resistance is per IEC 60068-2-6.