Schneider Electric VW3A46171 — AC Drive (VFD) 480V

VW3A46171 Passive Filter, 190 A, 480 V, for Altivar Drives

MPNVW3A46171
Active

Schneider Electric Altivar series passive filter, VW3A46171, 190 A output, 480 V, 60 Hz, THDI 5 % for 110 kW drives.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A46171 — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A46171 — Input / Supply
ParameterValue
Rated supply voltage range480 V +/- 10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A46171 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 IP55 (enclosure mounting)

Environmental

VW3A46171 — Environmental
ParameterValue
Operating ambient temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C storage in original packaging -25...65 °C during transport
Vibration resistance2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6

Approvals

VW3A46171 — Approvals
ParameterValue
Standards complianceIEC 61000-2-4 IEC 61000-3-12 G5/4 engineering recommendation IEC 61000-3-4 IEC 61000-2-2 IEC 61000-3-2

Product details

The VW3A46171 is a passive harmonic filter from Schneider Electric's Altivar accessory range, designed to reduce current harmonics on the line side of variable-speed drives. It is rated for a continuous input current of 183 A and output current of 190 A, at a supply voltage of 480 V +/- 10 %, 60 Hz. Its primary job is to bring the total harmonic current distortion (THDI) down to 5 % when paired with an Altivar drive rated 110 kW / 150 hp — that includes the ATV61H, ATV71H, ATV61Q, ATV71Q, ATV630, and ATV930 families. That 5 % figure is a clean number for meeting IEC 61000-2-4 and G5/4 engineering recommendation limits.

At 190 A output, this filter is sized for a 110 kW / 150 hp drive — one filter per drive, no sharing. The 480 V +/- 10 % supply voltage matches North American 480 VAC three-phase panels; the 60 Hz line frequency is fixed, not 50/60 Hz auto-switching. Thermal losses run 1080 W, so panel ventilation or enclosure derating matters — the filter itself is IP20, but when mounted in an enclosure it can achieve IP55. Ambient operating range is 5...45 °C without derating; above that, derate 3 % per °C up to 60 °C. Power factor correction is not the goal here — cos phi varies with load (1 at 150 % line current, 0.99 at 100 %, 0.85 at 75 %). The filter's efficiency is 98 %, meaning about 2 % of throughput is lost as heat.

This is a line-side passive filter, installed between the mains supply and the drive input. Wiring terminals on the A/B block accept up to 90 mm² cable; the control terminals (X1-1...X2-3) take 2.5 mm². One filter per drive, and the drive family list covers the ATV630 and ATV930 wall-mount variants at 110 kW.

Frequently asked questions

Where can I buy VW3A46171 and how do I get a price?

The VW3A46171 is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is VW3A46171's listed THDI?

The VW3A46171 achieves THDI of 5 % when paired with any of the listed 110 kW / 150 hp Altivar drives (ATV61H, ATV71H, ATV61Q, ATV71Q, ATV630, ATV930).

What compliance standards does VW3A46171 meet?

The filter complies with IEC 61000-2-4, IEC 61000-3-12, G5/4 engineering recommendation, IEC 61000-3-4, IEC 61000-2-2, and IEC 61000-3-2.