The 355 A input / 369 A output rating sets the hard ceiling for continuous current. The filter can handle 1.5× nominal current for 60 seconds — enough for motor acceleration transients but not a sustained overload. For drives above 250 kW, the evidence shows multiple filters are required in parallel: three filters per drive for the 560 kW ATV61H/Q, two for the 400 hp ATV71H, and one for the 200–220 kW range. Plan the panel space and busbar connections accordingly. Operating temperature range is 5–45 °C without derating; above that, derate 3 % per °C up to 60 °C. At altitudes above 1000 m, derate 5 % per additional 1000 m. The IP20 rating suits enclosed panel mounting; IP55 is achievable with the optional enclosure mount. Vibration resistance follows IEC 60068-2-6 at 0.7 gn from 13.2 to 150 Hz.
For BOM planning, the active lifecycle means no imminent end-of-life risk, but the large current rating and multi-filter configurations for high-power drives make lead-time verification prudent before committing to a production schedule.