Schneider Electric VW3A46174 — AC Drive (VFD) 480V

Schneider VW3A46174 Passive Filter, 369 A, 480 V, 60 Hz

MPNVW3A46174
Active

Schneider Electric Altivar series, VW3A46174 passive filter, 355 A input / 369 A output, 480 V ±10 %, 60 Hz, THDI ≤5 %.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A46174 — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A46174 — Input / Supply
ParameterValue
Rated supply voltage range480 V +/- 10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A46174 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 IP55 (enclosure mounting)

Environmental

VW3A46174 — Environmental
ParameterValue
Operating ambient temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C storage in original packaging -25...65 °C during transport
Vibration resistance2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6

Approvals

VW3A46174 — Approvals
ParameterValue
Standards complianceIEC 61000-2-4 IEC 61000-3-4 G5/4 engineering recommendation IEC 61000-3-12 IEC 61000-2-2 IEC 61000-3-2

Product details

The 355 A input / 369 A output rating sets the hard ceiling for continuous current. The filter can handle 1.5× nominal current for 60 seconds — enough for motor acceleration transients but not a sustained overload. For drives above 250 kW, the evidence shows multiple filters are required in parallel: three filters per drive for the 560 kW ATV61H/Q, two for the 400 hp ATV71H, and one for the 200–220 kW range. Plan the panel space and busbar connections accordingly. Operating temperature range is 5–45 °C without derating; above that, derate 3 % per °C up to 60 °C. At altitudes above 1000 m, derate 5 % per additional 1000 m. The IP20 rating suits enclosed panel mounting; IP55 is achievable with the optional enclosure mount. Vibration resistance follows IEC 60068-2-6 at 0.7 gn from 13.2 to 150 Hz.

For BOM planning, the active lifecycle means no imminent end-of-life risk, but the large current rating and multi-filter configurations for high-power drives make lead-time verification prudent before committing to a production schedule.

Frequently asked questions

What is the power factor correction range?

Cos φ reaches 1 at 150 % of line current, 0.99 at 100 % of line current, and 0.85 at 75 % of line current, covering the typical operating band of a variable-speed drive.

What compliance standards does VW3A46174 meet?

The filter complies with IEC 61000-2-4, IEC 61000-3-4, G5/4 engineering recommendation, IEC 61000-3-12, IEC 61000-2-2, and IEC 61000-3-2. Insulation is Class F.

MPN
VW3A46174